Reset Key - Omron K7GE-MG User Manual

Insulation resistance monitoring device
Hide thumbs Also See for K7GE-MG:
Table of Contents

Advertisement

4-6

Reset Key

Press the Reset Key in the Operation
Level for at least 3 seconds to
perform the power ON reset process
and return to the default.
The defined measurement values,
alarm outputs, and alarm output
indicator are all cleared.
Even if automatic measurement is in
progress, pressing the Reset Key will
force the measurement to end. The
same applies to manual
measurement.
This key can also be used to clear
the alarm output after checking its
status at the work site during the
occurrence of an alarm.
Also, if there are many channels, it takes around 10 minutes from the start till the end of automatic
measurement, but if automatic measurement is started unintentionally, this key can be used to stop it
immediately.
The reset operation can also be executed by a communications command.
The Reset Key is disabled in the Initial Setting Level, Communications Setting Level, and Protect Level. Use it with
caution.
Insulation Resistance Monitoring Device User's Manual (N224)
4 Functions Related to Measurement
Power ON
Note
Power ON reset
Operation Level
Measuring
stopped
TRIG
FIN
LVL
----
Measurement
1
standby
CH
MANU ERR
AGE
RESET
TRIG
FIN
LVL
-9#2
Measurement
3
completed
At least
CH
3 seconds
MANU
ERR
AGE
Trigger signal ON
Measurement
RESET
completed
At least
TRIG
FIN
3 seconds
LVL
--66
1
CH
MANU
ERR
AGE
Automatic measurement
in progress
Power ON reset is a reset process
that runs when the power turns ON.
MANU
MEAS
MANU
Or, 3 minutes
MEAS
from the time
of startup
At least 1 second
At least
TRIG
FIN
3 seconds
LVL
9#0
1
CH
RESET
MANU
ERR
AGE
Manual measurement
At least
3 seconds
4 - 25
4

Advertisement

Table of Contents
loading

Table of Contents