System Error - Omron K7GE-MG User Manual

Insulation resistance monitoring device
Hide thumbs Also See for K7GE-MG:
Table of Contents

Advertisement

4 Functions Related to Measurement
4-7

System Error

A system error is an error which causes the K7GE-MG to be unable to perform the functions that it was
primarily meant to perform.
In a normal state in which a system error does not occur, self-diagnosis error output is turned ON, but
due to the occurrence of a system error, the self-diagnosis error output is turned OFF, and an external
notification is sent.
The display and output when a system error occurs are as follows:
Main Unit
Probe Unit
A system error occurs due to the following two causes.
Duplication of the channel numbers of Probe Units
Hardware failure
If a system error occurs, first of all, make sure that there is no duplication of
the channel numbers of Probe Units. If the same channel number is set,
correct it and turn ON the power again. If the K7GE-MG can be started
normally, you can use it in this condition.
If the channel numbers are not duplicated, a hardware failure has occurred.
Contact your OMRON representative for repairs.
4 - 26
Name
Main display
ERR indicator
Self-diagnosis error output
ALM 1 and ALM 2 output
Alarm output indicator
LVL/CH display
Other indicators
MEAS indicator
ALM indicator
Discharge of electric charge
Apply Megger voltage
Operation
8888 is lit
Lit
OFF (normally ON)
All OFF
Not lit
Not lit
All not lit
Not lit
Stops
Stops
Insulation Resistance Monitoring Device User's Manual (N224)
MEAS
MEAS
MEAS
TRIG
FIN
LVL
8888
1
ALM
ALM
ALM
CH
CH1
CH2
CH3
MANU
ERR
AGE
ALM 2
ALM 1