Read Variable Area Command - Omron K7GE-MG User Manual

Insulation resistance monitoring device
Hide thumbs Also See for K7GE-MG:
Table of Contents

Advertisement

STX
Node number
H'02
MRC
2
The FINS-mini commands that the K7GE-MG supports are as follows:
MRC/SRC
'0101'
'0102'
'3005'
6-8-2

Read Variable Area Command

The FINS-mini text of the Read Variable Area command is as follows:
Command text:
MRC
'01'
2
MRC/SRC
Variable type
Read start address
Bit position
Number of elements
Response text:
MRC
'01'
2
MRC/SRC
Response code
Read data
Insulation Resistance Monitoring Device User's Manual (N224)
Sub-address
Completion code
FINS-mini command text
'00'
SRC
MRES
SRES
2
2
2 bytes
Command
Read Variable Area
Write Variable Area
Operation Command
SRC
Variable type
Read start address
'01'
'80'
2
2
The Read Variable Area command. Specify '0101'.
Specify '80' for the K7GE-MG.
Specify the address of the variable area to start reading. Refer to 6-3 Variable Area
Map on page 6-5.
Always set the bit position to '00'.
Specify the number of variables to read. You can specify up to 20 variables
(H'0014).
SRC
Response codes MRES/SRES
'01'
2
4
The content from the command text is entered as-is.
The result of executing the command is entered. Refer to Response codes: on
page 6-18.
Contains the read value.
ETX
BCC
H'03
Data
Bit position
Number of elements
'00'
4
2
Read data
Number of elements × 4 bytes
6 Remote Monitoring
'0000' to '0014'
4 bytes
6
6 - 17

Advertisement

Table of Contents
loading

Table of Contents