Trigger Signal Reverse - Omron K7GE-MG User Manual

Insulation resistance monitoring device
Hide thumbs Also See for K7GE-MG:
Table of Contents

Advertisement

5-6

Trigger Signal Reverse

Level
Characters
Initial
tr-r
Setting
In the K7GE-MG, automatic measurement starts when the
trigger signal turns ON.
Trigger Signal Reverse sets whether the external contacts
connected to the trigger input terminals turning OFF is
treated as trigger signal ON (enabled), or the external
contacts turning ON is treated as trigger signal ON.
The operation procedure for the Trigger Signal Reverse setting parameter is shown as follows:
Procedure
1.
Press the Level Key for at least 3 seconds in the Operation
Level to move to the Initial Setting Level.
The LVL/CH display will indicate 0, and the LVL indicator will light
to show that the Initial Setting Level has been entered.
2.
Press the Mode Key several times to display tr-r.
3.
Press the Shift Key to enter the monitoring state.
The setting value is displayed.
4.
Press the Shift Key again to move to the setting change state.
The value that can be changed starts flashing.
5.
Use the Up Key to change the setting value.
6.
Press the Mode Key to move to the next setting parameter.
The changed setting value is saved in the internal memory.
Insulation Resistance Monitoring Device User's Manual (N224)
Range of setting
Default
values
value
OFF/ON
OFF
5 Using Setting Parameters
Description
External contact ON/OFF logic that turns the
trigger signal ON
Trigger Signal Reverse = OFF
External
contact OFF
ON
Trigger
signal
3 seconds
Trigger Signal Reverse = ON
ON
ON
5
TRIG
FIN
LVL
mxch
0
MANU
ERR
AGE
TRIG
FIN
LVL
tr-r
0
MANU
ERR
AGE
TRIG
FIN
LVL
off
0
MANU
ERR
AGE
TRIG
FIN
LVL
off
0
MANU
ERR
AGE
TRIG
FIN
LVL
on
0
MANU
ERR
AGE
TRIG
FIN
LVL
mtwt
0
MANU
ERR
AGE
5 - 13

Advertisement

Table of Contents
loading

Table of Contents