Omron K7GE-MG User Manual page 42

Insulation resistance monitoring device
Hide thumbs Also See for K7GE-MG:
Table of Contents

Advertisement

2 Procedure
Wire all connections.
To be safe, always attach a
fuse (2 A max., fast-blow
type) in the wiring from the
Probe Unit to the load.
The figure shows a
simplified view of the wiring
for status output during
measurement, and ALM 1
and ALM 2 outputs. Use a
suitable relay according to
the switching capacity of the
output transistor.
The K7GE-MG provides an
output transistor with
specifications of 24 VDC
(+10%) and 50 mA max.
Supply the operation power from a system different from that of the load. If the same system is used, the power
supply to the K7GE-MG will turn OFF when the load contactor turns OFF, and you may not be able to perform
measurement.
2 - 4
MC
M
Trigger
input
L3
L2
3
4
1
3
PE
Probe Unit 1
7
2
1
Operation
power supply
17
18
17
18
Status output during
measurement
Insulation Resistance Monitoring Device User's Manual (N224)
MC-a
M
M
L3
L2
L3
1
3
Probe Unit 2
Probe Unit 3
Main Unit
13
14
15
16
ALM 1
ALM 2
L2
1
3

Advertisement