Omron K7GE-MG User Manual page 32

Insulation resistance monitoring device
Hide thumbs Also See for K7GE-MG:
Table of Contents

Advertisement

1 Overview
Terminal Section: Main Unit
(A)
(B)
(C)
(F)
(G)
Terminal
Symbol
Number
(A)
1 and 2
(B)
3 and 4
(C)
5 and 6
(D)
7
(E)
NC
(F)
13 and 14 ALM 1 output
(G)
15 and 16 ALM 2 output
(H)
17 and 18 Status output
(I)
19 and 20 Self-diagnosis
Perform the wiring according to Section 3 Installation and Wiring.
1 - 12
(D)
(E)
(H)
(I)
Name
Operation
Connect the operation power supply to the Main Unit.
power supply
Trigger input
Input terminals of the external contact from where a trigger signal is
applied.
No. 3: Collector of the NPN transistor, No. 4: Emitter of the NPN transistor
RS-485
Connect the RS-485 communications line.
No. 5: +, No. 6: -
PE
A protective earthing terminal.
NC
Do not connect anything to this terminal.
Compares the measurement value and alarm value 1, and outputs an
alarm.
No. 13: Collector of the NPN transistor, No. 14: Emitter of the NPN
transistor
Compares the measurement value and alarm value 2, and outputs an
alarm.
No. 15: Collector of the NPN transistor, No. 16: Emitter of the NPN
transistor
Provides notification that measurement is in progress. The output is
during
normally open (OFF) You can use this output to design an interlock circuit
measurement
to prevent accidental restart of the load during measurement operation.
No. 17: Collector of the NPN transistor, No. 18: Emitter of the NPN
transistor
Provides notification about system error in the Main Unit. The output is
error output
normally closed (ON).
No. 19: Collector of the NPN transistor, No. 20: Emitter of the NPN
transistor
Operation
Insulation Resistance Monitoring Device User's Manual (N224)