Functions
 Logging function
PGR1C
PVS1C
(Electric power
(Electric power
/leakage)
/voltage sag)
O: With function
X: Without function
Six data logging areas have been prepared. Each area can save 588 pieces of data (up to
6 items can be set.)
• Data logging cycle can be selected from among 5 minutes, 10 minutes, 30 minutes, 1 hour,
2 hours, 6 hours, 12 hours, and 24 hours, and is controlled by specifying 0:00 of the
internal clock in the main unit as the starting point.
Example
Every 5 min
Every 10 min
Every 30 min
Every hour
Every 2 hours
Every 6 hours
Every 12 hours
Every 24 hours
For logging, after measurement data within a logging cycle is saved, data is reset to start
the measurement at the next cycle. For example, setting logging cycle of 5 min and
voltage MAX accumulates voltage MAX values every 5 min.
The number of days for which log data can be saved differs depending on logging cycles.
Every 5 min
Every 10 min
Every 30 min
Every hour
Every 2 hours
Every 6 hours
Every 12 hours
Every 24 hours
• For logging items that can be set, refer to Page A-15.
 CT signal detection
PGR1C
PVS1C
(Electric power
(Electric power
/leakage)
/voltage sag)
O: With function
X: Without function
When the CT, ZCT is connected, and the current whose measurement value is 2% of the
standard current is supplied continuously for 10 or more seconds, the targeted LED lights.
* Even when the low-cut function forcibly sets the current measurement value to 0, CT
signal detection turns LED ON, if the actually flowing current is more than 2% of the
standard current.
3-6
VSU1B
(Voltage sag)
(Voltage/current)
: When the logging function is set to 18:12, April 1, 2012 based on
the time of the internal clock in the main unit.
: Saved at 18:15, April 1, 2012. Every 5 min after that
: Saved at 18:20, April 1, 2012. Every 10 min after that
: Saved at 18:30, April 1, 2012. Every 30 min after that
: Saved at 19:00, April 1, 2012. Every hour after that
: Saved at 20:00, April 1, 2012. Every 2 hours after that
: Saved at 0:00, April 2, 2012. Every 6 hours after that
: Saved at 0:00, April 2, 2012. Every 12 hours after that
: Saved at 0:00, April 2, 2012. Every 24 hours after that
: 2 days + 1 hour
: 4 days + 2 hours
: 12 days + 6 hours
: 24 days + 12 hours
: 49 days
: 147 days
: 294 days
: 588 days
VSU1B
(Voltage sag)
(Voltage/current)
×
VAU1B
CTD8E
(CT extension)
(ZCT extension)
×
VAU1B
CTD8E
(CT extension)
(ZCT extension)
ZCT8E
×
ZCT8E