Fault Counts Group

Fault Counts Window
The "Fault Counts" window displays all the faults that can occur and the number of times
those faults happened since the drive was originally powered-up. The information in this
window cannot be edited or cleared.
# of Occurrences
The "# of Occurrences" column displays the number of times each fault has occurred since
the drive was originally powered up.

Advanced Tab

This tab is reserved for very infrequently used parameters that sometimes need to be adjusted
to solve certain application problems. This tab is not normally visible and it is only rarely
necessary. If any parameter in this tab is not at default, then it will automatically be enabled
when starting PowerTools FM.
All the setups here are effective for all modes used and for both the (Main) Default Operating
Mode and the Alternate Operating Mode.

Drive Ambient Group

Drive Ambient Temperature -
Firmware Version B4 and later drives.
Drive Ambient Temperature is a parameter which will let the drive know the air temperature
around the drive heat sink while the system is under normal operating conditions. If the actual
ambient temperature is higher than 40°C (104°F), setting the Drive Ambient Temperature
parameter to the actual temperature will help to protect the drive by activating the Shunt Fault
at an appropriate time.
Figure 49:
EN Drive Ambient View