NOTE:
GP Output n Options and descriptions common to GP outputs 1 to 30.
4 - 16
Manager Reset
After the removal of the input and closure of the flow control valve,
loading is paused for the time set within the Clear/Reconnect timer.
However the operator is given the option of restarting the load once
the input is restored to an active state prior to the Clear/Reconnect
expiry. Once the timer expires the loading computer is locked out
from loading until a Manager Reset is performed by entering the
Manager Reset password (see section 4.2) into the instrument at
the password prompt or sending the MR SLIP command.
If emergency stop input is disconnected during loading the load is
terminated. A new load cannot be started unless the Manager Reset
Password is entered into the instrument at the Password Prompt.

4.5 General Purpose Outputs (24)

Use the General Purpose Outputs sub-menu of the System menu to
assign the available General Purpose Outputs to a range of available
functions.
GP Output
Model 1010 Application Pack CB
Programming Manual
CONFIGURE MESSAGES
GENERAL PURPOSE OUTPUTS
- GP OUTPUT 29 - BB16/BB17
GP OUTPUT 30 - BB18/BB17
-
-
- GP OUTPUT 1 - A9/A10
1 -
1 -
DISPLAY CONTRAST
-
INITIAL MESSAGES
GP OUTPUT 2 - A11/A12
-
-
GP OUTPUT 3 - A13/A17
-
- MANAGER MESSAGES
PRESS ENTER TO SELECT
PRESS ENTER TO SELECT
Relay
1
A1
2
A2
3
A3
4
A4
5
A5
6
A6
7
B1
8
B2
9
B3
10
B4
11
B5
12
B6
27
24
Terminal
A9/A10
A11/A12
A13/A17
A14/A17
A15/A17
A16/A17
BA1/BA2
BA2/BA3
BA4/BA5
BA5/BA6
BA7/BA8
BA9/BA8
Part No.: 4418024 - Rev. 1