Tension Electronics PFEA111/112, User Manual
Chapter 3 Commissioning

3.13.5 Handling of Measurement Data through Profibus

3.13.5.1 Miscellaneous Meny

WebTension
From CurrentOutput
> 5 s
FastSetUp
Miscellaneous
Presentation-
Menu
Menu
SetObject
NominalLoad
ServiceMenu
ZeroSet
SetWrapGain
VoltageOutput
CurrentOutput
Miscellaneous
Menu
ServiceMenu
3-28
Two web tension measurement values are transferred through Profibus:
Value 1 has the same step response time as "voltage output"
Value 2 has the same step response time as "current output".
The scaling of "voltage output" and "current output" does not affect the measurement values
transferred through Profibus.
If zero set has been performed, the zero set values are transferred through Profibus.
For scaling of Profibus measurement values, see
Each measurement value has 16 bit, 2-complement representation (Integer 16).
Use this menu for scaling Profibus measuring values
Profibus On/Off
ZZ
ProfibusAddress
ZZZ
To
(Only shown if
Profibus is On)
MeasuringRange
XXX.XXX N
(Only shown if
Profibus is On)
LoadDivision
XXX.XXX N
(Only shown if
Profibus is On)
SetFactory
Default
Figure 3-20. Profibus Scaling
Section
3.13.5.2.
Profibus On/Off
[ZZ]
ProfibusAddress
[ZZZ]
MeasuringRange
[XXX.XXX] N
AreYouSure
3BSE029380R0101 Rev C
ActionDone
(shown for 1 s.)