Profibus Dp Fieldbus Couplers/Controllers 750-333(/0Xx-000), 750-833(/0Xx-000); Profinet Io Fieldbus Couplers 750-375(/025-000), 750-377(/025-000); Table 48: General Module/Channel Parameters; Table 49: General Module/Channel Parameters - WAGO 750 Manual

Table of Contents

Advertisement

84
Appendix
10.1.2.2
PROFIBUS DP Fieldbus Couplers/Controllers 750-333(/0xx-000), 750-
833(/0xx-000)
The aforementioned fieldbus coupler/ controller allow channel-specific
parameterization of behavior at diagnosis.

Table 48: General Module/Channel parameters

Parameter
Diagnosis
Channel x (x = 0...3)
*)
Default setting
10.1.2.3

PROFINET IO Fieldbus Couplers 750-375(/025-000), 750-377(/025-000)

The aforementioned fieldbus couplers allow channel-specific parameterization of
the behavior during diagnostics, as well as parameterization of the associated
user limit values.

Table 49: General Module/Channel parameters

Parameters
Channel Diagnostics
Channel x (x = 0...3)
Diagnostics:
Measurement
Underrange
Channel x (x = 0...3)
Manual
Version 1.0.0
All manuals and user guides at all-guides.com
Value
*)
0 (disabled)
1 (enabled)
Value
*)
0 (false)
1 (true)
0 (false)
*)
1 (true)
WAGO-I/O-SYSTEM 750
750-471 4AI U/I Diff Galv
Explanation
The fieldbus coupler/controller signals a diagnosis, if
at least one channel of the I/O module reports the
following events:
- Measurement range overflow
- Measurement range underflow
- Overload
- Wire break
Diagnostics reported by the I/O module do not lead to
the signaling of a diagnosis by the fieldbus
coupler/controller.
Diagnostics reported by the I/O module lead to the
signaling of a diagnosis by the fieldbus
coupler/controller.
Explanation
An error on the respective signal channel does
not lead to transmission of a diagnostic alarm
nor entry in the diagnostics database of the
station proxy.
An error on the respective signal channel leads
to transmission of a diagnostic alarm. The
respective error leads to an entry in the
diagnostics database of the station proxy.
A measurement underrange on the respective
signal channel does not lead to transmission of
a diagnostic alarm nor entry in the diagnostics
database of the station proxy.
Provided that the channel diagnostics of the
respective signal channel has been activated, a
measurement underrange leads to transmission
of a diagnostic alarm and entry in the
diagnostics database of the station proxy.