Power Supply Concept - WAGO I/O-SYSTEM 750 Manual

2ai 4-20ma hart ex i 2-channel analog input; hart; intrinsically safe, 2ai 4-20ma hart ne43 ex i 2-channel analog input; hart; namur ne43; intrinsically safe
Table of Contents

Advertisement

46
Connect Devices
6.2

Power Supply Concept

Ex i I/O modules shall only be supplied via Ex i 24 VDC power supply
module!
Ex i I/O modules shall only be operated with an Ex i 24 VDC power supply
module.
Keep the air and creep distances between intrinsically safe segments!
The maximum current available from the 750-606 or 750-625/000-001 Ex-i
Supply Module is 1 A.
If the use of further 24 VDC Ex i Supply modules is necessary for reasons of
extent of utilization, four Separation Modules (750-616) must be used to
guarantee the distance between the intrinsically safe segments.
Do not exceed maximum current via power contacts!
The maximum current available from the Supply Module Ex i (750-606 or 750-
625/000-001) is 1 A.
When configuring the system, ensure that this current is not exceeded.
If exceeded, an additional potential feed module must be used.
Further information about explosion prevention!
Further information about explosion prevention can be found in section "Use in
Hazardous Environments"!
The Ex i I/O module receives the 24 V voltage supply for the field level from an
upstream Ex i I/O module or from an Ex i power supply module via the power
contacts used as blade contacts. It then provides this potential to subsequent I/O
modules via the power contacts used as spring contacts.
Manual
Version 1.4.0
WAGO-I/O-SYSTEM 750
750-484 2AI 4-20mA HART Ex i

Advertisement

Table of Contents
loading

This manual is also suitable for:

750-484750-484/000-001