Configuration

3 Configuration

3.1 IP Settings

3
3
All IP-related parameters are located in parameter group
12-0* IP Settings:
Parameter 12-00 IP Address Assignment.
Parameter 12-01 IP Address.
Parameter 12-02 Subnet Mask.
Parameter 12-03 Default Gateway.
Parameter 12-04 DHCP Server.
Parameter 12-05 Lease Expires.
Parameter 12-06 Name Servers.
Parameter 12-07 Domain Name.
Parameter 12-08 Host Name.
Parameter 12-09 Physical Address.
The EtherNet/IP control cassette offers several ways of IP
address assignment.
Setting up the frequency converter with a manually
assigned IP address
Parameter
Parameter 12-00 IP Address Assignment
Parameter 12-01 IP Address
Parameter 12-02 Subnet Mask
Parameter 12-03 Default Gateway
Table 3.1 Set-up Parameters for Manually
Assigned IP Address
1) Class C IP address example. Any valid IP address can be entered.
NOTICE
A power cycle is necessary after setting the IP
parameters manually.
Setting up the frequency converter with automatically
(BOOTP/DHCP) assigned IP address or via the hardware
switches
Parameter
Parameter 12-00 IP Address Assignment
Parameter 12-01 IP Address
Parameter 12-02 Subnet Mask
Parameter 12-03 Default Gateway
Table 3.2 Set-up Parameters for Automatically
Assigned IP Address
6
EtherNet/IP
By IP address assigned by DHCP/BOOTP server or hardware
switches, the assigned IP address and subnet mask can be
read out in parameter 12-01 IP Address and
parameter 12-02 Subnet Mask. In parameter 12-04 DHCP
Server, the IP address of the found DHCP or BOOTP server
is shown. For DHCP only: The remaining lease-time can be
read out in parameter 12-05 Lease Expires.
Parameter 12-09 Physical Address reads out the MAC
address of the option, which is also printed on the label of
the option. If using fixed leases together with DHCP or
BOOTP, the physical MAC address is linked with a fixed IP
address.
NOTICE
If no DHCP or BOOTP reply has been received after 4
attempts (for example, if the DHCP/BOOTP server has
been powered off), the option returns to the last good
known IP address.
Parameter 12-03 Default Gateway is optional and only used
in routed networks.
Optional parameters used with domain name server
systems:
Value
[0] MANUAL
192.168.0.xxx
1)
1)
255.255.255.0
If DHCP or BOOTP is selected as IP address assignment,
Optional
these parameters are read-only.

3.2 Ethernet Link Parameters

Parameter group 12-1* Ethernet Link Parameters holds
Ethernet Link information:
NOTICE
The Ethernet link parameters are unique per port.
Value
[1] DHCP/[2] BOOTP
Parameter 12-10 Link Status and parameter 12-11 Link
Read only
Duration show information on the link status per port.
Read only
Parameter 12-10 Link Status show Link or No Link according
Read only
to the status of the present port.
Parameter 12-11 Link Duration show the duration of the link
on the present port. If the link is broken, the counter
resets.
Danfoss A/S © 06/2016 All rights reserved.
Parameter 12-06 Name Servers.
Parameter 12-06 Name Servers.
Parameter 12-08 Host Name.
Parameter 12-10 Link Status.
Parameter 12-11 Link Duration.
Parameter 12-12 Auto Negotiation.
Parameter 12-13 Link Speed.
Parameter 12-14 Link Duplex.
MG07H102

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents