Troubleshooting

6 Troubleshooting

6.1 Step-by-step Troubleshooting

6.1.1 LED Status
The EtherNet/IP interface has 3 bicolored LEDs that allow
fast and detailed diagnosis. Each LED is linked to its unique
part of the EtherNet/IP interface, see Table 6.1.
State
6
6
Standby
Device operational
Major recoverable fault
Major unrecoverable
fault
Self-test
Table 6.2 MS: Module Status
State
No connections
Connected
Connection timeout
Duplicate IP
Self-test
Table 6.3 NS1+NS2: Network Status (1 per Port)
6.1.2 No Communication with the
Frequency Converter
Check: Link status
If CIP connection is not established, the status of the
Ethernet link cannot be directly identified using the LEDs.
Verify presence of the link via parameter 12-10 Link Status.
Verify that the link is constantly present via
parameter 12-11 Link Duration.
The parameter shows the duration of the present link and
is preset to 00:00:00:00 when the link is broken.
34
EtherNet/IP
LED
Green:
Green:
Red:
Red:
Red:
Green:
LED
Green:
Green:
Red:
Red:
Red:
Green:
Danfoss A/S © 06/2016 All rights reserved.
LED label
Module status. Reflects the activity on the
MS
EtherNet/IP stack.
Network status 1. Reflects the activity on Ethernet
NS1
port 1.
Network status 2. Reflects the activity on Ethernet
NS2
port 2.
Table 6.1 LED Label
Flashing green
The device needs commissioning.
Solid green
The device is operational.
Flashing red
The device has detected a recoverable fault (MAR).
Solid red
The device has detected an unrecoverable fault
(MAU).
Flashing red/
The EIP option is in self-test mode.
green
Flashing green
There are no established CIP connections to the
device.
Solid green
There is at least 1 established CIP connection to
the device.
Flashing red
1 or more CIP connections have timed out.
Solid red
The IP address assigned to the device is already in
use.
Flashing red/
The EIP option is in self-test mode.
green
Check: Cabling
In rare cases of cabling misconfiguration, the option may
show the presence of a link, but no communication is
running. Exchange the cable if in doubt.
Check: IP address
Verify that the option has a valid IP address (refer to
parameter 12-01 IP Address). When the option has identified
a duplicate IP address, NS LEDs are solid red. When the
option is set up for BOOTP or DHCP, verify that a BOOTP or
DHCP server is connected in parameter 12-04 DHCP Server.
If no server is connected, the parameter shows:
000.000.000.000.
Description
Description
Description
MG07H102