Parameters

5.3 Parameter List

5.3.1 Introduction
Changes during operation
True means that the parameter can be changed while the
frequency converter is in operation. False means that the
frequency converter must be stopped before a change can
be made.
4 set-up
All set-ups: The parameter can be set individually in each
of the 4 set-ups, for example, 1 single parameter can have
4 different data values.
1 set-up: The data value is same in all set-ups.
5.3.2 Parameter List
Parameter
Parameter 8-01 Control Site
Parameter 8-02 Control Source
Parameter 8-03 Control Timeout
Time
Parameter 8-04 Control Timeout
Function
Parameter 8-07 Diagnosis Trigger
Parameter 8-10 Control Word Profile
Parameter 8-14 Configurable
Control Word CTW
Parameter 8-19 Product Code
Parameter 8-30 Protocol
Parameter 8-31 Address
Parameter 8-32 Baud Rate
Parameter 8-33 Parity / Stop Bits
Parameter 8-35 Minimum Response
Delay
Parameter 8-36 Maximum Response
Delay
Parameter 8-37 Maximum Inter-
char delay
Parameter 8-42 PCD Write Configu-
ration
Parameter 8-43 PCD Read Configu-
ration
Parameter 8-50 Coasting Select
Parameter 8-51 Quick Stop Select
Parameter 8-52 DC Brake Select
Parameter 8-53 Start Select
Parameter 8-54 Reversing Select
Parameter 8-55 Set-up Select
Parameter 8-56 Preset Reference
Select
Parameter 8-57 Profidrive OFF2
Select
MG07H102
Programming Guide
Default value
4 set-up
[0] Dig. & ctrl. word
All set-ups
All set-ups
1
1 set-up
[0] Off
1 set-up
[0] Disable
1 set-up
[0] FC profile
All set-ups
[1] Profile default
All set-ups
1 set-up
[0] FC
1 set-up
1
1 set-up
[2] 9600 Baud
1 set-up
[0] Even Parity, 1 Stop
1 set-up
Bit
0.010
1 set-up
1 set-up
0.025 s
1 set-up
[0] None
2 set-ups
[0] None
1 set-up
[3] Logic OR
All set-ups
[3] Logic OR
All set-ups
[3] Logic OR
All set-ups
[3] Logic OR
All set-ups
[3] Logic OR
All set-ups
[3] Logic OR
All set-ups
[3] Logic OR
All set-ups
[3] Logic OR
All set-ups
Danfoss A/S © 06/2016 All rights reserved.
Data
Description
type
2
Integer 8
3
Integer 16
4
Integer 32
5
Unsigned 8
6
Unsigned 16
7
Unsigned 32
9
Visible string
33
Normalized value 2 bytes
35
Bit sequence of 16 boolean variables
54
Time difference w/o date
Table 5.2 Data Type
Change during
Conversion
operation
index
TRUE
TRUE
TRUE
TRUE
TRUE
TRUE
TRUE
TRUE
TRUE
TRUE
TRUE
TRUE
TRUE
TRUE
TRUE
TRUE
TRUE
TRUE
TRUE
TRUE
TRUE
TRUE
TRUE
TRUE
TRUE
Type
Int8
Int16
Int32
Uint8
Uint16
Uint32
VisStr
N2
V2
TimD
Type
Uint8
Uint8
-1
Uint16
Uint8
Uint8
Uint8
Uint8
0
Uint32
Uint8
0
Uint8
Uint8
Uint8
-3
Uint16
-3
Uint16
-3
Uint16
Uint8
Uint8
Uint8
Uint8
Uint8
Uint8
Uint8
Uint8
Uint8
Uint8
31
5
5

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents