AMI Turbitrace
Default Values
Input:
72
If Function = Control upw. or dnw:
Parameter: ...................................................................Meas. value
Settings: Actuator: ...........................................................Frequency
Settings: Pulse Frequency: .............................................. 120/min
Settings: Control Parameters: Setpoint: ......................... 100 FNU
Settings: Control Parameters: P-band:.......................... 5.00 FNU
Parameter: .................................................................. Sample flow
Settings: Actuator: ...........................................................Frequency
Settings: Pulse Frequency: .............................................. 120/min
Settings: Control Parameters: Setpoint: ........................... 20.0 l/h
Settings: Control Parameters: P-band:............................... 1.0 l/h
Common settings:
Settings: Control Parameters: Reset time: ............................... 0 s
Settings: Control Parameters: Derivative Time: ....................... 0 s
Settings: Control Parameters: Control Timeout:................... 0 min
Settings: Actuator:................................................. Time proportional
Cycle time: ............................................................................. 60 s
Response time: ..................................................................... 10 s
Settings: Actuator.......................................................... Motor valve
Run time: ............................................................................... 60 s
Neutral zone: ...........................................................................5%
If Function = Timer:
Mode:.................................................................................... Interval
Interval:................................................................................. 1 min
Mode: ....................................................................................... daily
Start time: ........................................................................00.00.00
Mode:..................................................................................... weekly
Calendar; Start time: .......................................................00.00.00
Calendar; Monday to Sunday:.................................................. Off
Run time: ................................................................................... 10 s
Delay:........................................................................................... 5 s
Signal output:............................................................................. cont
Output/Control: .......................................................................... cont
Active ............................................................................when closed
Signal Outputs ........................................................................... hold
Output/Control .............................................................................. off
Fault..............................................................................................no
Delay.......................................................................................... 10 s
A-96.250.131 / 050220