F Input Terminal Delay - Toshiba G7 Operation Manual

Adjustable speed drive
Hide thumbs Also See for G7:
Table of Contents

Advertisement

F134
OUT5 Terminal Assignment
Program ⇒ Terminal Selection Parameters ⇒ Output Terminal
Assignment ⇒ 5
This parameter sets the functionality of the OUT5 terminals to 1 of the 60
possible functions that are listed in
The on and off delay times of the OUT5 terminals may be adjusted to provide
more response time to the device that is connected to the output terminals.
In addition, the output terminals must be specified as Normally Open or
Normally Closed.
OUT6 Terminal Assignment
Program ⇒ Terminal Selection Parameters ⇒ Output Terminal
Assignment ⇒ 6
This parameter sets the functionality of the OUT6 terminals to 1 of the 60
possible functions that are listed in
The on and off delay times of the OUT6 terminals may be adjusted to provide
more response time to the device that is connected to the output terminals.
In addition, the output terminals must be specified as Normally Open or
Normally Closed.
OUT7 Terminal Assignment
Program ⇒ Terminal Selection Parameters ⇒ Output Terminal
Assignment ⇒ 7
This parameter sets the functionality of the OUT7 terminals to 1 of the 60
possible functions that are listed in
The on and off delay times of the OUT7 terminals may be adjusted to provide
more response time to the device that is connected to the output terminals.
In addition, the output terminals must be specified as Normally Open or
Normally Closed.

F Input Terminal Delay

Program ⇒ Terminal Selection Parameters ⇒ Input Terminal Delays ⇒
F
This parameter delays the response of the ASD to any change in the F terminal
input by the programmed value.
The delay may be increased to provide additional electrical noise immunity or
to prevent the ASD from responding to contact bounce or chatter.
80
Table 9 on pg.
81.
Table 9 on pg.
81.
Table 9 on pg.
81.
Direct Access Number — F134
Parameter Type — Selection List
Factory Default — UL
Changeable During Run — No
Direct Access Number — F135
Parameter Type — Selection List
Factory Default — RCH (Specified
Speed)
Changeable During Run — No
Direct Access Number — F136
Parameter Type — Selection List
Factory Default — Overcurrent
Prealarm
Changeable During Run — No
Direct Access Number — F140
Parameter Type — Numerical
Factory Default — 8.0
Changeable During Run — No
Minimum — 2.0
Maximum — 200.0
Units — mS
G7 ASD Operation Manual
F140