Jump Frequency #3 Bandwidth; Jump Frequency Processing - Toshiba G7 Operation Manual

Adjustable speed drive
Hide thumbs Also See for G7:
Table of Contents

Advertisement

F274
Jump Frequency #3
Program ⇒ Special Control Parameters ⇒ Jump Frequencies
Same as Jump Frequency #1
are to be jumped (see the plus-or-minus value setting at F275). When multiple
jump frequencies overlap, the system will recognize the lowest and the highest
frequencies as one jump range.

Jump Frequency #3 Bandwidth

Program ⇒ Special Control Parameters ⇒ Jump Frequencies
This parameter establishes a plus-or-minus value for Jump Frequency #3
(
F274).

Jump Frequency Processing

Program ⇒ Special Control Parameters ⇒ Jump Frequencies ⇒ Jump
Frequency Processing
This parameter determines if the output frequency of the ASD or the PID
feedback signal will be used as a reference for determining the Jump
Frequency range.
See
F270
for further information on the Jump Frequency settings.
Settings:
Process Amount (use PID feedback)
Output Frequency
Preset Speed #8
Program ⇒ Pattern Run Control ⇒ Preset Speeds ⇒ 8
This parameter assigns an output frequency to binary number 1000 and is
identified as Preset Speed #8. The binary number is applied to S1 – S4 of the
Control Terminal Strip to output the Preset Speed (see
information on this parameter).
Preset Speed #9
Program ⇒ Pattern Run Control ⇒ Preset Speeds ⇒ 9
This parameter assigns an output frequency to binary number 1001 and is
identified as Preset Speed #9. The binary number is applied to S1 – S4 of the
Control Terminal Strip to output the Preset Speed (see
information on this parameter).
G7 ASD Operation Manual
(
F270) and is used when multiple frequencies
F018
F018
Direct Access Number — F274
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — Max. Freq. (F011)
Units — Hz
Direct Access Number — F275
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 30.0
Units — Hz
Direct Access Number — F276
Parameter Type — Selection List
Factory Default — Process Amount
Changeable During Run — Yes
Direct Access Number — F287
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — Lower Limit (F013)
for further
Maximum — Upper Limit (F012)
Units — Hz
Direct Access Number — F288
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — Lower Limit (F013)
for further
Maximum — Upper Limit (F012)
Units — Hz
F288
109