Analog 2 Terminal Adjustment - Toshiba G7 Operation Manual

Adjustable speed drive
Hide thumbs Also See for G7:
Table of Contents

Advertisement

F675

Analog 2 Terminal Adjustment

Program ⇒ Meter Terminal Adjustment Parameters ⇒ Analog 2
This parameter adjusts the coefficient of the circuit to obtain an output that
corresponds with a known input.
This function is used in the calibration of external signal measuring devices
(DVM, counters, etc.).
FP Terminal Setting
Program ⇒ Terminal Selection Parameters ⇒ FP
This parameter commands the multifunction programmable FP terminal to
monitor the value of 1 of 31 possible system functions. As the monitored
function changes in magnitude or frequency, the pulse count of the FP output
pulse train changes in direct proportion to changes in the monitored function.
As the monitored value goes up so does the pulse count of the FP output.
Note:
The duty cycle of the output pulse train remains at 65 ±5.0 µS.
Possible assignments for this output terminal are listed in
FP Terminal Adjustment
Program ⇒ Terminal Selection Parameters ⇒ FP
This parameter sets the full-scale reading of the FP Terminal. The full-scale
reading of the monitored variable selected in
Display Units for Voltage and Current
Program ⇒ Utility Parameters ⇒ Display Units
This parameter sets the unit of measurement for current and voltage values
displayed on the EOI.
Settings:
%
V/A
Hz Per User-defined Unit
Program ⇒ Utility Parameters ⇒ Display Units
This parameter allows the user to input a quantity to be displayed on the EOI
that is proportional to the output frequency of the drive.
This feature is useful when the output of a process is moved along at a rate that
is proportional to the output frequency of the drive.
Frequency Display Resolution
Program ⇒ Utility Parameters ⇒ Display Units
The parameter sets the number of decimal places to be displayed during non-
Accel/Decel functions.
164
Table 7 on pg.
61.
F676
may be set here.
Direct Access Number — F675
Parameter Type — Numerical
Factory Default — 512
Changeable During Run — Yes
Minimum — 1
Maximum — 1280
Direct Access Number — F676
Parameter Type — Selection List
Factory Default — Output Frequency
Changeable During Run — Yes
Direct Access Number — F677
Parameter Type — Numerical
Factory Default — 3.840
Changeable During Run — Yes
Minimum — 1.000
Maximum — 43.200
Units — kHz
Direct Access Number — F701
Parameter Type — Selection List
Factory Default — %
Changeable During Run — Yes
Direct Access Number — F702
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 200.0
Units — Hz/UDU
Direct Access Number — F703
Parameter Type — Numerical
Factory Default — 0.1
Changeable During Run — Yes
Minimum — 1
Maximum — 0.01
G7 ASD Operation Manual
F703

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents