Toshiba G7 Operation Manual page 103

Adjustable speed drive
Hide thumbs Also See for G7:
Table of Contents

Advertisement

F216
RX Speed Reference Setpoint #1 (%)
Program ⇒ Frequency Setting Parameters ⇒ Speed Reference
Setpoints ⇒ RX
This parameter is used to set the direction, gain, and bias of the RX input
terminal when this terminal is used as the control input while operating in the
Speed Control or the Torque Control mode.
Perform the following setup to allow the system to receive control input at the
RX input terminal:
Program ⇒ Fundamental Parameters ⇒ Standard Mode Selection ⇒
Command Mode ⇒ Use Control Terminal Strip.
Program ⇒ Fundamental Parameters ⇒ Standard Mode Selection ⇒
Frequency Mode #1⇒ Use RX.
Provide a Run command (F or R).
Gain and Bias Settings
When operating in the Speed Control mode, the settings that determine the
direction, gain, and bias of the RX terminal are:
RX Speed Reference Setpoint #1 (frequency)
the RX input signal level that represents RX Speed Reference
Setpoint #1 (frequency): F216,
RX Speed Reference Setpoint #2 (frequency)
the RX input signal level that represents RX Speed Reference
Setpoint #2 (frequency)
When operating in the Torque Control mode, the settings that determine the
direction, gain, and bias of the RX terminal are:
RX Torque Reference Setpoint #1 (%)
the RX input signal level that represents the RX Torque Reference
Setpoint #1 (%): F216,
RX Torque Reference Setpoint #2 (%)
the RX input signal level that represents the RX Torque Reference
Setpoint #2 (%): F218.
Once set, as the RX input voltage changes, the directional information, the
output frequency, or the output torque of the drive will vary in accordance with
the above settings.
This parameter sets the RX input level that represents RX Reference Setpoint
#1 (direction/torque/frequency). This value is entered as -100 to +100% of the
-10 to +10 VDC RX input signal range.
The input signal may be trimmed using
RX Speed Reference Setpoint #1 (frequency)
Program ⇒ Frequency Setting Parameters ⇒ Speed Reference
Setpoints ⇒ RX
This parameter is used to set the direction, gain, and bias of the RX input
terminal when this terminal is used as the control input while operating in the
Speed Control mode.
See
F216
for further information on this setting.
This parameter sets RX Speed Reference Setpoint #1 (frequency) and is the
frequency that is associated with the setting of F216.
G7 ASD Operation Manual
(
F217
(
F219
:
F218.
(
)
F220
,
(
)
F221
, and
F474
(Bias) and
F475
(Gain).
Direct Access Number — F216
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — -100.0
Maximum — 100.0
Units — %
Frequency Settings
)
,
)
, and
Torque Settings
Direct Access Number — F217
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — -80.0
Maximum — +80.0
Units — Hz
F217
97

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents