F218
RX Speed Reference Setpoint #2 (%)
Program ⇒ Frequency Setting Parameters ⇒ Speed Reference
Setpoints ⇒ RX
This parameter is used to set the direction, gain, and bias of the RX input
terminal when this terminal is used as the control input while operating in the
Speed Control or the Torque Control mode.
See
F216
for further information on this setting.
This parameter sets the RX input level that represents RX Reference Setpoint
#2 (frequency) (direction/torque/frequency). The range of values for this
parameter is -100 to +100% of the -10 to +10 VDC RX input signal range.
RX Speed Reference Setpoint #2 (frequency)
Program ⇒ Frequency Setting Parameters ⇒ Speed Reference
Setpoints ⇒ RX
This parameter is used to set the direction, gain, and bias of the RX input
terminal when this terminal is used as the control input while operating in the
Speed Control mode.
See
F216
for further information on this setting.
This parameter sets RX Speed Reference Setpoint #2 (frequency) and is the
frequency that is associated with the setting of F218.
RX Torque Reference Setpoint #1 (%)
Program ⇒ Torque Setting Parameters ⇒ Setpoints ⇒ RX
This parameter is used to set the direction, gain, and bias of the RX input
terminal when this terminal is used as the control input while operating in the
Torque Control mode.
This is accomplished by establishing an associated V/f output pattern for a
given RX input level and motor load.
See
F216
for further information on this setting.
This parameter sets RX Torque Reference Setpoint #1 (%) and is the output
torque value that is associated with setting of F216. This value is entered as
-250 to +250% of the rated torque.
RX Torque Reference Setpoint #2 (%)
Program ⇒ Torque Setting Parameters ⇒ Setpoints ⇒ RX
This parameter is used to set the direction, gain, and bias of the RX input
terminal when this terminal is used as the control input while operating in the
Torque Control mode.
This is accomplished by establishing an associated V/f output pattern for a
given RX input level and motor load.
See
F220
for further information on this setting.
This parameter sets RX Torque Reference Setpoint #2 (%) and is the output
torque value that is associated with setting of F218. This value is entered as
-250 to +250% of the rated torque.
98
Direct Access Number — F218
Parameter Type — Numerical
Factory Default — +100.0
Changeable During Run — Yes
Minimum — -100.0
Maximum — +100.0
Units — %
Direct Access Number — F219
Parameter Type — Numerical
Factory Default — +80.0
Changeable During Run — Yes
Minimum — -80.0
Maximum — +80.0
Units — Hz
Direct Access Number — F220
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — -250.0
Maximum — +250.0
Units — %
Direct Access Number — F221
Parameter Type — Numerical
Factory Default — +100.0
Changeable During Run — Yes
Minimum — -250.0
Maximum — +250.0
Units — %
G7 ASD Operation Manual
F221