F723
Torque Limit Group
No path available (Direct Access Only)
While operating using the LED Keypad Option this parameter is used to select
1 of 4 preset positive torque limits to apply to the active motor. The settings of
profiles 1 – 4 may be setup at F441, F444, F446, and F448, respectively.
Settings:
1
2
3
4
Note:
If using the LCD EOI, press ESC from the Frequency
Command screen to access this parameter.
Feedback in Panel Mode
No path available (Direct Access Only)
While operating using the LED Keypad Option this parameter Enables/
Disables PID feedback control.
Settings:
Enabled
Disabled
Note:
If using the LCD EOI, press ESC from the Frequency
Command screen to access this parameter.
LED Option Override Multiplication Gain
Program ⇒ Feedback Parameters ⇒ Override Control
If operating using the LED Keypad Option this parameter provides a value to
be used in the event that Setting is selected for the Frequency Override
Multiplying Input (F661).
LOD Control and Stopping Method
Program ⇒ Special Control Parameters ⇒ Low Output Disable Function
⇒ LOD
Enables/Disables the Low Output Disable function and, if enabled, selects a
stopping method.
Settings:
Disabled
Enabled — Decel Stop
Enabled — Coast Stop
LOD Start Level (Hz)
Program ⇒ Special Control Parameters ⇒ Low Output Disable Function
⇒ LOD Start Level (Hz)
The Low Output Disable Start Level sets the output frequency threshold that,
if exceeded, will initiate the LOD function if properly configured.
166
Direct Access Number — F723
Parameter Type — Selection List
Factory Default — 1
Changeable During Run — Yes
Direct Access Number — F724
Parameter Type — Selection List
Factory Default — Enabled
Changeable During Run — Yes
Direct Access Number — F729
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — -100.00
Maximum — 100.00
Direct Access Number — F731
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — Yes
Direct Access Number — F732
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — Max. Freq.
Units — Hz
G7 ASD Operation Manual
F732