F190
Custom V/f Five-Point Setting #1 Frequency
Program ⇒ Special Control Parameters ⇒ V/f Five-Point Setting
The Custom V/f Five-Point Setting #1 Frequency setting establishes the
frequency that is to be associated with the voltage setting of
Five-Point Setting #1 Voltage).
The V/f five-point settings define a custom volts per hertz relationship for the
startup output of the ASD.
To enable this function, set the V/f Pattern (F015) selection to Custom V/f
Curve.
Custom V/f Curves may be useful in starting high inertia loads such as rotary
drum vacuum filters.
Custom V/f Five-Point Setting #1 Voltage
Program ⇒ Special Control Parameters ⇒ V/f Five-Point Setting
The Custom V/f Five-Point Setting #1 Voltage establishes the percentage of
the output voltage that is to be associated with the frequency setting of
(Custom V/f Five-Point Setting #1 Frequency).
See
F190
for additional information on custom V/f curves.
Custom V/f Five-Point Setting #2 Frequency
Program ⇒ Special Control Parameters ⇒ V/f Five-Point Setting
The Custom V/f Five Point Setting #2 Frequency sets the frequency to be
associated with parameter
See
F190
for additional information on custom V/f curves.
Custom V/f Five-Point Setting #2 Voltage
Program ⇒ Special Control Parameters ⇒ V/f Five-Point Setting
The Custom V/f Five-Point Setting #2 Voltage establishes the percentage of
the output voltage that is to be associated with the frequency setting of
(Custom V/f Five Point Setting #2 Frequency).
See
F190
for additional information on custom V/f curves.
G7 ASD Operation Manual
F193
(Custom V/f Five Point Setting #2 Voltage).
Direct Access Number — F190
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — No
F191
(Custom V/f
Minimum — 0.0
Maximum — 299
Units — Hz
Direct Access Number — F191
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — No
F190
Minimum — 0.0
Maximum — 100.0
Units — %
Direct Access Number — F192
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — No
Minimum — 0.0
Maximum — 299
Units — Hz
Direct Access Number — F193
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — No
F192
Minimum — 0.0
Maximum — 100.0
Units — %
F193
89