Alarms And Trips; Alarms, Trips, And Troubleshooting - Toshiba G7 Operation Manual

Adjustable speed drive
Hide thumbs Also See for G7:
Table of Contents

Advertisement

Alarms, Trips, and Troubleshooting

Alarms and Trips

This section lists the available user-notification codes of the EOI display and provides information that
assists the user in the event that a Fault is incurred. The User Notification codes are displayed as an
indication that a system function or system condition is active (i.e., ATN,ATN2, DB, and DBON). The
code is displayed on the EOI for the duration of the activation.
If a user setting or an ASD parameter has been exceeded, or if a data transfer function produces an
unexpected result, a condition that is referred to as a Fault is incurred.
An Alarm is an indication that a Fault is imminent if existing operating conditions continue unchanged.
An Alarm may be associated with an output terminal to notify the operator of the condition remotely,
close a contact, or engage a brake. At the least, an Alarm will cause an alarm code to appear on the EOI
display.
Table 10
ASD.
In the event that the condition that caused the Alarm does not return to its normal operating level within a
specified time, the ASD Faults and a Trip is incurred (Fault and Trip are sometimes used
interchangeably). A Trip is a safety feature, and is the result of a Fault, that disables the ASD system in
the event that a subsystem of the ASD is malfunctioning, or one or more of the variables listed below
exceeds its normal range (time and/or magnitude).
• Current,
• Voltage,
• Speed,
• Temperature,
• Torque, or
• Load.
See
Table 12 on pg. 176
The operating conditions at the time of the trip may be used to help determine the cause of the trip. Listed
below are operating conditions that may be used to assist the operator in correcting the problem or that the
ASD operator should be prepared to discuss when contacting Toshiba's Customer Support for assistance.
• What trip information is displayed?
• Is this a new installation?
• Has the system ever worked properly and what are the recent modifications (if any)?
• What is the ASD/Motor size?
• What is the CPU version and revision level?
• What is the EOI version?
• Does the ASD trip when accelerating, running, decelerating, or when not running?
• Does the ASD reach the commanded frequency?
• Does the ASD trip without the motor attached?
• Does ASD trip with an unloaded motor?
G7 ASD Operation Manual
lists the 16 possible Alarm codes that may be displayed during operation of the G7
for a listing of the potential Trips and the associated probable causes.
173