F733
LOD Start Time
Program ⇒ Special Control Parameters ⇒ Low Output Disable Function
⇒ LOD Start Time
The Low Output Disable Start Time sets the amount of time that the LOD
Start Level criteria must be met and maintained for the LOD function to be
initiated.
LOD Setpoint Boost (Hz)
Program ⇒ Special Control Parameters ⇒ Low Output Disable Function
⇒ LOD Setpoint Boost (Hz)
The Low Output Disable feature adds the user-input frequency value to the
commanded frequency.
LOD Boost Time
Program ⇒ Special Control Parameters ⇒ Low Output Disable Function
⇒ LOD Boost Time
The Low Output Disable Boost Time sets the on-time timer for the LOD
Boost function.
Once expired, the LOD Boost function ceases.
LOD Feedback Level (Hz)
Program ⇒ Special Control Parameters ⇒ Low Output Disable Function
⇒ LOD Feedback Level (Hz)
The Low Output Disable Feedback Level sets a frequency level that, until the
output of the ASD drops below this setting, the Restart Delay Timer does not
start.
LOD Restart Delay Time
Program ⇒ Special Control Parameters ⇒ Low Output Disable Function
⇒ LOD Restart Delay Time
The Low Output Disable Restart Delay Time sets the time that, once expired
and all standard ASD requirements are met, normal ASD operation resumes.
Communication Baud Rate (logic)
Program ⇒ Communication Setting Parameters ⇒ Communication
Settings
This parameter plays a role in the setup of the communications network by
establishing the Baud Rate of the communications link.
The communications network includes other ASDs and Host/Control computers
that monitor the status of the ASD(s), transfers commands, and loads or
modifies the parameter settings of the ASD.
Changes made to this parameter require that the power be cycled (Off then On)
for the changes to take effect.
G7 ASD Operation Manual
Direct Access Number — F733
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — 3600.0
Units — Seconds
Direct Access Number — F734
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — Max. Freq.
Units — Hz
Direct Access Number — F735
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — 3600.0
Units — Seconds
Direct Access Number — F736
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — Max. Freq.
Units — Hz
Direct Access Number — F737
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — 3600.0
Units — Seconds
Direct Access Number — F800
Parameter Type — Numerical
Factory Default — 9600
Changeable During Run — Yes
Minimum — 1200
Maximum — 9600
Units — BPS
F800
167