Link Reactor Information - Toshiba G7 Operation Manual

Adjustable speed drive
Hide thumbs Also See for G7:
Table of Contents

Advertisement

Link Reactor Information

Selection of a link reactor (DCL) is often application specific. This document will provide guidelines for
selecting link reactors for the G7 series of drives.
The 600 Volt series drives above 15 HP allow for the reactor to be mounted internal to the drive. All other
G7 drives require that the DCL be mounted externally.
When selecting and mounting an external DCL, the air flow around the reactor, the thermal capability of
the reactor, the allowable voltage loss, and the amount of harmonic reduction required will be
considerations.
Model Number
VT130G7U
2080B
2110B
2160B
2220B
2270B
4110B
4160B
4220B
4270B
4330B
4400B
4500B
4600B
4750B
410KB
6060B
6120B
6160B
6220B
6270B
6330B
6400B
6500B
6600B
6750B
610KB
612KB
615KB
620KB
625KB
G7 ASD Operation Manual
Table 21. DCL Selection Table.
DCL Part
DCL Inductance
Number
36350
36351
36376
36353
36355
36358
36359
36360
36361
36363
36364
36365
36365
36366
42769
36356
36359
36359
36360
36362
36361
36363
36363
36364
36365
36366
36367
41443
41443
45259
DCL
(mH)
(Amps)
0.40
30.0
0.30
38.0
0.20
57.0
0.20
76.0
0.10
114
1.30
20.0
0.90
29.0
0.70
39.0
0.50
50.0
0.40
75.0
0.30
88.0
0.20
114.0
0.20
114.0
0.20
141.0
0.14
205.0
2.50
11.0
0.90
29.0
0.90
29.0
0.70
39.0
0.50
55.0
0.50
50.0
0.40
75.0
0.40
75.0
0.30
88.0
0.20
114.0
0.20
141.0
0.15
175.0
0.19
260.0
0.19
260.0
0.10
360.0