F375
Current Control Integral Gain
Program ⇒ Feedback Parameters ⇒ PG Settings
This parameter sets the degree and rate at which the output frequency will be
allowed to change when prompted by changes in the output current.
The larger the value entered here, the quicker/more the drive responds to
changes in feedback.
Speed Loop Proportional Gain
Program ⇒ Feedback Parameters ⇒ PG Settings
This parameter sets the Proportional Gain (sensitivity) of the drive when
monitoring the PG signal to control speed. The larger the value entered here,
the more sensitive the drive is to changes in the received feedback and the
quicker it responds.
Speed Loop Integral Gain
Program ⇒ Feedback Parameters ⇒ PG Settings
This parameter sets the response time of the Speed Loop Integral Gain. The
smaller the value here, the more pronounced (quicker) the effect of the integral
function.
Motor Counter Data
Program ⇒ Feedback Parameters ⇒ PG Settings
This parameter sets the pulses-per-revolution displayed at the Monitor screen
when using a shaft-mounted encoder for speed control. This setting is used for
display purposes only and does not affect the speed control of the system.
If zero is selected here then the setting at
determines the pulses-per-revolution to be displayed at the Monitor screen.
Settings:
Selection 0 —
F370
setting
Selection 1 — 256 pulses/revolution
Selection 2 — 512 pulses/revolution
Selection 3 — 1024 pulses/revolution
Selection 4 — 2048 pulses/revolution
Selection 5 — 4096 pulses/revolution
Speed Loop Parameter Ratio
Program ⇒ Feedback Parameters ⇒ PG Settings
Contact Toshiba's Marketing Department for information on this parameter.
124
F370
(Electronic Gear Setting)
Direct Access Number — F375
Parameter Type — Numerical
Factory Default — (ASD-dependent)
Changeable During Run — No
Minimum — 100.0
Maximum — 1250
Direct Access Number — F376
Parameter Type — Numerical
Factory Default — (ASD-dependent)
Changeable During Run — Yes
Minimum — 3.2
Maximum — 1000
Direct Access Number — F377
Parameter Type — Numerical
Factory Default — (ASD-dependent)
Changeable During Run — Yes
Minimum — 10.0
Maximum — 200.0
Direct Access Number — F378
Parameter Type — Selection List
Factory Default — Selection 0
Changeable During Run — No
Minimum — Selection 0
Maximum — Selection 5
Direct Access Number — F379
Parameter Type — Numerical
Factory Default — 1.00
Changeable During Run — No
Minimum — 0.01
Maximum — 10.00
G7 ASD Operation Manual
F379