Toshiba G7 Operation Manual page 91

Adjustable speed drive
Hide thumbs Also See for G7:
Table of Contents

Advertisement

F163
OUT4 Off Delay
Program ⇒ Terminal Selection Parameters ⇒ Output Terminal Delays
⇒ OUT4
This parameter delays the opening of the OUT4 output terminals by the
programmed value (see waveforms at F160).
The delay may be increased to allow the devices that are connected to OUT4 to
respond.
OUT5 Off Delay
Program ⇒ Terminal Selection Parameters ⇒ Output Terminal Delays
⇒ OUT5
This parameter delays the opening of the OUT5 output terminals by the
programmed value (see waveforms at F160).
The delay may be increased to allow the devices that are connected to OUT5 to
respond.
OUT6 Off Delay
Program ⇒ Terminal Selection Parameters ⇒ Output Terminal Delays
⇒ OUT6
This parameter delays the opening of the OUT6 output terminals by the
programmed value (see waveforms at F160).
The delay may be increased to allow the devices that are connected to OUT6 to
respond.
OUT7 Off Delay
Program ⇒ Terminal Selection Parameters ⇒ Output Terminal Delays
⇒ OUT7
This parameter delays the opening of the OUT7 output terminals by the
programmed value (see waveforms at F160).
The delay may be increased to allow the devices that are connected to OUT7 to
respond.
Motor #2 Base Frequency
Program ⇒ Motor Parameters ⇒ Motor Set #2
The Motor #2 Base Frequency setting is the frequency at which the output
voltage of the ASD reaches its maximum setting. The #2 Maximum Output
Voltage is set at F171.
This parameter is used only when the parameters for motor set #2 are
configured and selected. Motor set #2 may be selected by a properly configured
input terminal.
For proper motor operation, the Base Frequency should be set for the name-
plated frequency of the motor.
G7 ASD Operation Manual
Direct Access Number — F163
Parameter Type — Numerical
Factory Default — 2.0
Changeable During Run — No
Minimum — 2.0
Maximum — 200.0
Units — mS
Direct Access Number — F164
Parameter Type — Numerical
Factory Default — 2.0
Changeable During Run — No
Minimum — 2.0
Maximum — 200.0
Units — mS
Direct Access Number — F165
Parameter Type — Numerical
Factory Default — 2.0
Changeable During Run — No
Minimum — 2.0
Maximum — 200.0
Units — mS
Direct Access Number — F166
Parameter Type — Numerical
Factory Default — 2.0
Changeable During Run — No
Minimum — 2.0
Maximum — 200.0
Units — mS
Direct Access Number — F170
Parameter Type — Numerical
Factory Default — 60.0
Changeable During Run — Yes
Minimum — 25.0
Maximum — 299.0
Units — Hz
F170
85