Toshiba G7 Operation Manual page 83

Adjustable speed drive
Hide thumbs Also See for G7:
Table of Contents

Advertisement

Table 8 (Continued). Discrete Input Terminal Assignment Selections and Descriptions.
28 — Binary Bit 1 — See selection 27 above.
29 — Binary Bit 2 — See selection 27 above.
30 — Binary Bit 3 — See selection 27 above.
31 — Binary Bit 4 — See selection 27 above.
32 — Binary Bit 5 — See selection 27 above.
33 — Binary Bit 6 — See selection 27 above.
34 — Binary Bit 7 — See selection 27 above.
35 — Forced Stop — Activating this terminal terminates the Run command regardless of the Command Mode setting and
initiates the programmed stopping method.
36 — Stop Key Emulation — Activating this terminal terminates the Run command being received from communications
devices and initiates the programmed stopping method.
37 — Reserved — No operation.
38 — Reserved — No operation.
39 — Reserved — No operation.
40 — Reserved — No operation.
41 — Reserved — No operation.
42 — Reserved — No operation.
43 — Binary Data Write — This terminal serves two functions:
1) While operating in the Use Binary/BCD input mode, each momentary connection of this terminal to CC transfers the
speed/torque Binary Bit (0 – MSB) settings to the motor.
2) The Motorized Pot frequency command will be saved during power down or reset by setting
setting an input terminal to 43:binary Data Write. If the drive is running and the Binary Data Write terminal is
active when an event occurs (Fault, Power off), the Motorized Pot frequency command will be restored upon power-
up or reset.
44 — Motorized Pot Up (MOP) — Momentarily connecting this terminal to CC causes an increase in motor speed for the
duration of the connection until the Upper Limit is reached. The Frequency Mode setting must be set to Motorized
Pot. Simulation. The MOP acceleration rate is determined by the
45 — Motorized Pot Down (MOP) — Momentarily connecting this terminal to CC causes a decrease in motor speed for the
duration of the connection until the Lower Limit is reached. The Frequency Mode setting must be set to Motorized
Pot. Simulation. The MOP deceleration rate is determined by the
46 — Motorized Pot Clear — Connecting this terminal to CC clears the last Motorized Pot frequency settings (see
further information on this setting).
47 — Momentary Push Run — When connected to CC this terminal setting starts the motor.
48 — Momentary Push Stop — When connected to CC this terminal setting stops the motor.
49 — Forward/Reverse — This setting operates in conjunction with another terminal being set to the Run/Stop (50) function.
When configured to Run (Run/Stop to CC), the make or break of this connection to CC changes the direction of the
motor.
50 — Run/Stop — This terminal enables the motor to run when connected to CC and disables the motor when the connection
is broken.
51 — Line Power Bypass — This function operates in conjunction with the Line Power Switching frequency setting (F355).
An enabled check box at Program
terminal setting enables this function.
Once configured (including this terminal connection to CC), the frequency setting of Line Power Switching (Hz)
establishes the speed at which the drive terminates its output and routes commercial power to the motor.
G7 ASD Operation Manual
Terminal Selection Parameters
F500
setting.
F501
setting.
Line Power Switching (At) and this input
F108
to Store and
F108
for
77

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents