Fault Screen Display
Typeform Error
U Phase Short Circuit
V Phase Short Circuit
W Phase Short Circuit
Note:
The event that caused the Trip(s) must be corrected or must decrease to less than the threshold
value required to cause the trip to allow for a Reset to be recognized. In the event of multiple
active trips, the trip displayed will remain until all faults are corrected and all trips are cleared.

Viewing Trip Information

In the event that the condition causing an Alarm does not return to the normal operating level within a
specified time, the ASD Faults and a Trip is incurred.
When a trip occurs, the resultant error information may be viewed either from the
(Program ⇒ Monitor Setup ⇒ Trip History), the
Setup ⇒ Trip Monitor From ASD), or from the Monitor screen.
Trip History
The Trip History screen records the system parameters for up to 101 trips (RTC option required). The
recorded trips are numbered from zero to 100. Once the Trip History record reaches trip number 100, the
oldest recorded trip will be deleted with each new record stored (first-in first-out). The Trip # field may be
selected and scrolled through to view the recorded trip information for a given trip number. The monitored
parameters are listed in
the trip occurred).
Table 13. Trip History Record Parameters (RTC option required).
Trip records that are assigned zero and one are comprised of the full list of monitored parameters (32).
Trip records 2 – 18 are comprised of parameters 1 – 16. Trip records 19 – 100 are comprised of
parameters 1 – 7.
1) Trip Number
2) Trip Type
3) Time and Date
4) Frequency at Trip
5) Output Current
6) Output Voltage
7) Direction
8) Frequency Reference
180
• Firmware information (typeform) loaded into the Gate Driver board is
inconsistent with the device in which the firmware is being used.
• The Gate Driver board has been replaced.
• The Gate Driver board is defective.
• Low impedance at the U lead of the ASD output.
• Low impedance at the V lead of the ASD output.
• Low impedance at the W lead of the ASD output.
Table 13
as At-trip Recorded Parameters (parameter readings at the time that

At-trip Recorded Parameters

9) Bus Voltage
10) Discrete Input Status
11) OUT1/OUT2/FL Status
12) Timer
13) Post Compensation Frequency
14) Feedback (inst.)
15) Feedback (1 sec.)
16) Torque
Possible Causes
Trip Monitor From ASD
17) Torque Reference
18) Torque Current
19) Excitation Current
20) PID Value
21) Motor Overload
22) ASD Overload
23) DBR Overload
24) Motor Load
Trip History
screen
screen (Program ⇒ Monitor
25) ASD Load
26) DBR Load
27) Input Power
28) Output Power
29) Peak Current
30) Peak Voltage
31) PG Speed
32) PG Position
G7 ASD Operation Manual