Multi-Function Input Terminal; 10V Power Supply - Toshiba ETB003Z Instruction Manual

Expansion io card option 1
Table of Contents

Advertisement

3.2 Multi-function input terminal

Four output terminals can be added. Function is similar to that of the input terminals of
the inverter, so refer to the inverter instruction manual.
Parameter
Title
Input terminal selection 9 (LI1)
f119
Input terminal selection 10 (LI2)
f120
Input terminal selection 11 (LI3)
f121
Input terminal selection 12 (LI4)
f122
f144 * Input terminal 5~12 response time selection
* VF-PS1 does not have this parameter.
Monitor
Refer to the description on status monitor mode of inverter's instruction manual.
The input terminal status can be monitored by the input terminal status parameter
(fe06), and the parameter can be monitor by the serial communication.
fe06
bit No.
Symbol
Note: The LI5 ~ LI8 are the terminal function of the expansion IO card option 2.

3.3 -10V power supply

The frequency command can be input from RX terminal with pulse and negative voltage
using N10(-10V) and PP(+10V) power.
2k ohm
N10 (-10V)
Function
15
14
13
12
11
LI8
LI7
LI6
LI5
LI4
Inverter Terminal
PP (+10)
RX
Option Terminal
Adjustment range
0 - 135
0 - 135
0 - 135
0 - 135
2 - 200ms
10
9
8
7
LI3
LI2
LI1
S4
S3
Potentio meter
Center position: 0V command
Pulse side position: +10V command
Negative side position: -10V command
The recommended wiring cable length is
less than 1.5m with shielded cable.
11
E6581339⑥
Default setting
0
0
0
0
8
6
5
4
3
2
S2
S1
RES
ST
1
0
R
F

Advertisement

Table of Contents
loading

Table of Contents