Huawei UA5000 Manual page 84

Environment monitoring
Hide thumbs Also See for UA5000:
Table of Contents

Advertisement

UA5000 Universal Access Unit
Environment Monitoring
To...
Configure the battery
discharging test parameters
Configure the rectifier unit
parameter
Configure the load and
battery high-temperature
power-off parameters
Configure the environment
monitoring parameters
Configure the external
extended digital parameters
Query the configuration
parameters of the power
system
The following considers the configuration in the F01E400 cabinet as an example to describe the
process of configuring the environment monitoring parameters of the EPS30-4815AF.
1.
2.
3.
Issue 01 (2012-08-17)
Log in to the UA5000 through the maintenance terminal and add an EMU.
huawei(config)#emu add 0 POWER4845 0 0 RS232 POWER4830
Query the status of the EPS30-4815AF.
huawei(config)#display emu 0
--------------------------------------------------------------------
EMU name
: POWER4830
EMU type
: Pwr4845
EMU state
: Normal
Frame ID
: 0
Subnode
: 0
COM Port
: RS232
--------------------------------------------------------------------
Enter the environment monitoring configuration mode and query the default configuration.
huawei(config)#interface emu 0
huawei(config-if-power4845-0)#display power system parameter
EMU ID: 0
----------------------------------------------------------------------------
charge control state
equalizing Voltage : 56.500V
charge lmt quotiety: 0.150
battery number
battery 0 capacity : 130
battery Temperature Upper
Temp redeem quotiety: 100mV
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Run the Command...
power battery-test
power module-num
power temperature-off
power environment
power outside-digital
IDs of user-defined alarms in the digital parameters: IDs 1-20
are reserved alarm IDs in the system (1: AC_voltage; 2:
AC_switch; 3: Battery_voltage; 4: Battery_fuse; 5: Load_fuse;
6: Rectifier; 7: DC_power; 8: Cupboard_door; 9: Room_door;
10: Window; 11: Theft; 12: Wiring; 13: Fan; 14: Fire; 15: Fog;
16: Water; 17: Diesel; 18: Smell 19: Air_conditioner; 20:
SPD), and IDs 21-52 are alarm IDs allocated to other user-
defined alarms by users.
display power system parameter
Power system information
: automatic control
floating Voltage: 53.500V
equalizing time
: 1
AH
: 60
C
6 EPS30-4815AF Monitoring Solution
: 60 days
battery Temperature Lower : -40
C
78