UA5000 Universal Access Unit
Environment Monitoring
Item
Rectifier unit
parameter
Load and
battery high-
temperature
power-off
parameters
Environment
monitoring
parameters
Issue 01 (2012-08-17)
Data Plan for the
F01D500 Cabinet
Delays the time of the
discharging test: 1d
Number of rectifier
units: 2
Load high-temperature
power-off permission
status: forbid
Battery high-
temperature power-off
permission status: permit
Temperature for load
high-temperature
power-off: 70°C
Temperature for battery
high-temperature
power-off: 53°C
Upper alarm threshold of
the temperature: 68°C
Lower alarm threshold
of the temperature: -5°C
Upper alarm threshold of
the humidity: 80% RH
Lower alarm threshold
of the humidity: 10% RH
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
7 EPS75-4815AF Monitoring Solution
Remarks
This parameter is set according to the actual
requirements.
Default: 14d.
This parameter is set according to the actual
requirements. The EPS75-4815AF supports up to
two rectifier units.
Default value: 5.
This parameter is set according to the actual
requirements.
Default: forbid.
This parameter is set according to the actual
requirements.
Default: forbid.
This parameter is set according to the actual
requirements.
Default: 65°C.
This parameter is set according to the actual
requirements.
Default: 53°C.
This parameter is set according to the actual
requirements. When the actual temperature
reaches or is higher than the upper alarm
threshold, the system reports an alarm.
Default: 50°C.
This parameter is set according to the actual
requirements. When the actual temperature is
equal to or lower than the lower alarm threshold,
the system reports an alarm.
Default: 0°C.
This parameter is set according to the actual
requirements. When the actual humidity reaches
or is higher than the upper alarm threshold, the
system reports an alarm.
Default: 80% RH.
This parameter is set according to the actual
requirements. When the actual humidity is equal
to or lower than the lower alarm threshold, the
system reports an alarm.
Default: 10% RH.