UA5000 Universal Access Unit
Environment Monitoring
Table 7-21 Commands for configuring the EPS75-4815AF
To...
Add an EMU
Configure the battery charging
parameters
Configure the battery
management parameters and the
temperature compensation
parameters of the battery.
Configure the power supply load
power-off and battery set power-
off parameters
Configure the power distribution
parameters
Configure the battery
discharging test parameters
Configure the rectifier unit
parameter
Configure the load and battery
high-temperature power-off
parameters
Configure the environment
monitoring parameters
Configure the external extended
digital parameters
Query the configuration
parameters of the power system
The following considers the configuration in the F01D500 cabinet as an example to describe the
process of configuring the environment monitoring parameters of the EPS75-4815AF.
1.
Issue 01 (2012-08-17)
Log in to the PVM through the maintenance terminal and add an EMU.
huawei(config)#emu add 0 POWER4875L 0 0 RS232 POWER4875L
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
7 EPS75-4815AF Monitoring Solution
Run the Command...
emu add
power charge
power battery
power off
power supply-parameter
power battery-test
power module-num
power temperature-off
power environment
power outside-digital
IDs of user-defined alarms in the digital parameters: IDs
1-20 are reserved alarm IDs in the system (1: AC_voltage;
2: AC_switch; 3: Battery_voltage; 4: Battery_fuse; 5:
Load_fuse; 6: Rectifier; 7: DC_power; 8: Cupboard_door;
9: Room_door; 10: Window; 11: Theft; 12: Wiring; 13:
Fan; 14: Fire; 15: Fog; 16: Water; 17: Diesel; 18: Smell
19: Air_conditioner; 20: SPD), and IDs 21-52 are alarm
IDs allocated to other user-defined alarms by users.
display power system parameter
116