UA5000 Universal Access Unit
Environment Monitoring
Item
Environment
monitoring
parameters
External
extended
digital
parameters
Issue 01 (2012-08-17)
Data Plan for the
F01D500 Cabinet
Temperature for load
high-temperature
power-off: 70°C
Temperature for battery
high-temperature
power-off: 53°C
Upper alarm threshold of
the temperature: 68°C
Lower alarm threshold
of the temperature: -5°C
Upper alarm threshold of
the humidity: 80% RH
Lower alarm threshold
of the humidity: 10% RH
Digital parameter ID: 0
Valid level of digital
parameter 0: low level
Digital parameter ID: 1
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
8 ETP4890 Monitoring Solution
Remarks
This parameter is set according to the actual
requirements.
Default: 65°C.
This parameter is set according to the actual
requirements.
Default: 53°C.
This parameter is set according to the actual
requirements. When the actual temperature
reaches or is higher than the upper alarm
threshold, the system reports an alarm.
Default: 50°C.
This parameter is set according to the actual
requirements. When the actual temperature is
equal to or lower than the lower alarm threshold,
the system reports an alarm.
Default: 0°C.
This parameter is set according to the actual
requirements. When the actual humidity reaches
or is higher than the upper alarm threshold, the
system reports an alarm.
Default: 80% RH.
This parameter is set according to the actual
requirements. When the actual humidity is equal
to or lower than the lower alarm threshold, the
system reports an alarm.
Default: 10% RH.
This digital parameter is set according to the
actual requirements. The monitoring digital
parameter of the fan tray is set here to monitor the
fan tray. When the fan tray is faulty, the host
reports an alarm.
When the low level represents the valid level, the
host does not report an alarm in the case of low
level.
This digital parameter is set according to the
actual requirements. The monitoring digital
parameter of the fan tray is set here to monitor the
fan tray. When the fan tray is faulty, the host
reports an alarm.
143