Environment Monitoring
Item
Battery
management
parameters
Temperature
compensatio
n parameter
of the battery
Issue 01 (2012-08-17)
Data Plan for the
F01D500 Cabinet
Equalized charging
voltage of the battery:
56.5 V
Float charging voltage of
the battery: 53.5 V
Current-limiting
coefficient for battery
charging: 0.15
Interval of battery
equalized charging: 60
days
Number of battery sets: 1 This parameter is set according to the actual
Capacity of the battery
set: 75 AH
Upper temperature
threshold of the battery
set: 80°C
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
8 ETP4890 Monitoring Solution
Remarks
This parameter is set according to the actual
requirements. When setting the equalized
charging voltage of the battery, make sure that DC
overvoltage - 1 V > equalized charging voltage >
float charging voltage + 2 V, and that DC
undervoltage > load power-off voltage > battery
power-off voltage.
Default: 56.5 V.
This parameter is set according to the actual
requirements. When setting the float charging of
the battery, make sure that DC overvoltage - 1 V
> equalized charging voltage > float charging
voltage + 2 V, and that DC undervoltage > load
power-off voltage > battery power-off voltage.
Default: 53.5 V.
This parameter is set according to the actual
requirements. In the normal state, the current of
the power supply is not limited. The current-
limiting function is enabled when the charging
current of the battery set > current-limiting
coefficient x nominal capacity of the battery set.
Default value: 0.15.
This parameter is set according to the actual
requirements. If the continuous float charging
duration of the rectifier unit exceeds the preset
equalized charging interval, the battery enters the
equalized charging state.
Default: 60 days.
requirements. The number of battery sets can be
set to 0 or 1. That is, the system supports up to one
battery set.
Default value: 1.
The battery capacity is configured according to
the actual value. The F01D200 cabinet uses the
80 AH batteries, the F01D500 cabinet uses the
150 AH or 194 AH batteries, and the F01D1000
cabinet uses the 150 AH or 194 AH batteries.
Default: 65 AH.
This parameter is set according to the actual
requirements.
Default: 80°C.