Huawei UA5000 Manual page 117

Environment monitoring
Hide thumbs Also See for UA5000:
Table of Contents

Advertisement

UA5000 Universal Access Unit
Environment Monitoring
Item
Temperature
compensatio
n parameter
of the battery
Power
supply load
power-off
and battery
set power-off
parameters
Issue 01 (2012-08-17)
Data Plan for the
F01D500 Cabinet
Number of battery sets: 1 This parameter is set according to the actual
Capacity of the battery
set: 75 AH
Upper temperature
threshold of the battery
set: 80°C
Lower temperature
threshold of the battery
set: -20°C
Temperature
compensation
coefficient of the battery
set: 80 mV
Load power-off
permission status: forbid
Battery set power-off
permission status: permit
Load power-off voltage:
44 V
Battery set power-off
voltage: 43 V
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
7 EPS75-4815AF Monitoring Solution
Remarks
requirements. The number of battery sets can be
set to 0 or 1. That is, the system supports up to one
battery set.
Default value: 1.
The battery capacity is configured according to
the actual value. The F02A cabinet uses the 100
AH batteries, the F02AF cabinet uses different
external batteries according to the actual
conditions, the F01D200 cabinet uses the 80 AH
batteries, the F01D500 cabinet uses the 150 AH
or 194 AH batteries, and the F01D1000 cabinet
uses the 150 AH or 194 AH batteries.
Default: 65 AH.
This parameter is set according to the actual
requirements.
Default: 80°C.
This parameter is set according to the actual
requirements.
Default: -20°C.
This parameter is set according to the actual
requirements. The temperature compensation
coefficient refers to the variable of the float
charging voltage of the battery set when the
temperature of the battery set changes by every 1°
C.
Default: 80 mV.
This parameter is set according to the actual
requirements.
Default: forbid.
This parameter is set according to the actual
requirements.
Default: permit.
This parameter is set according to the actual
requirements.
Default: 44 V.
This parameter is set according to the actual
requirements.
Default: 43 V.
111

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents