UA5000 Universal Access Unit
Environment Monitoring
Item
Configuration Process
The monitoring parameters can be reported to the control board and the service processing board
only when the data for the EPS75-4815AF is configured correctly in the system.
Figure 7-14
the configuration.
Figure 7-14 Configuration process of the EPS75-4815AF
Configure the temperature compensation coefficient of
Configure the power supply load power-off and battery
Configure the battery discharging test parameters
Configure the environment monitoring parameters
Configure the external extended digital parameters
Issue 01 (2012-08-17)
Data Plan for the
F01D500 Cabinet
Digital parameter ID: 6
Valid level of digital
parameter 6: low level
shows the configuration process, and
Start
Add an EMU
Configure the battery charging parameters
Configure the battery management parameters
the battery
set power-off parameters
Configure the power distribution parameters
Configure the rectifier unit parameter
Configure the load and battery high-temperature
power-off parameters
End
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
7 EPS75-4815AF Monitoring Solution
Remarks
This digital parameter is set according to the
actual requirements. The digital monitoring
parameter of the MDF door status sensor is set
here to monitor the MDF door status. When the
door of the MDF compartment is open, the host
reports an alarm.
When the low level represents the valid level, the
host does not report an alarm in the case of low
level.