UA5000 Universal Access Unit
Environment Monitoring
5.
6.
7.
8.
9.
10. Configure the rectifier unit parameter.
11. Configure the load and battery high-temperature power-off parameters.
12. Configure the environment parameters.
13. Configure the extended digital parameters.
14. Query the information about the configured parameters and environment parameters of the
Issue 01 (2012-08-17)
If the planned data is the same as the query result, the parameters need not be configured.
If the parameters need to be modified, run the power charge command.
Configure the battery management parameters.
huawei(config-if-power4875l-0)#power battery parameter 0.15 60 1 150
Configure the temperature compensation coefficient of the battery.
If the planned data is the same as the query result, the parameters need not be configured.
If the parameters need to be modified, run the power battery temperature command.
Configure the power supply load power-off and battery set power-off parameters.
If the planned data is the same as the query result, the parameters need not be configured.
If the parameters need to be modified, run the power off command.
Configure the power distribution parameters.
If the planned data is the same as the query result, the parameters need not be configured.
If the parameters need to be modified, run the power supply-parameter command.
Configure the battery discharging test parameters.
huawei(config-if-power4875l-0)#power battery-test auto-test off-test forbid
time-test permit 180 1
huawei(config-if-power4875-0)#power module-num 2 1 2
huawei(config-if-power4875l-0)#power temperature-off load-off-state forbid
load-off-temperature 70 battery-off-state permit battery-off-temperature 53
l Configure the temperature parameters.
huawei(config-if-power4875l-0)#power environment temperature 68 -5 80 -20
l Configure the humidity parameters.
If the planned data is the same as the query result, the parameters need not be configured.
If the parameters need to be modified, run the power environment humidity command.
huawei(config-if-power4875l-0)#power outside_digital 0 available-level low-
level name Fan
huawei(config-if-power4875l-0)#power outside_digital 1 available-level low-
level name HABF_FAN
huawei(config-if-power4875l-0)#power outside_digital 3 available-level low-
level name SPD
huawei(config-if-power4875l-0)#power outside-digital 4 available-level high-
level name Smoke
huawei(config-if-power4875l-0)#power outside-digital 5 available-level low-
level name HEX
huawei(config-if-power4875l-0)#power outside-digital 6 available-level low-
level name MDF-door
power system.
huawei(config)#interface emu 0
huawei(config-if-power4875l-0)#display power system parameter
EMU ID: 0
----------------------------------------------------------------------------
charge control state
equalizing Voltage : 56.500V
charge lmt quotiety: 0.150
battery number
battery 0 capacity : 150
battery temperature test upper :
temperature redeem quotiety
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Power system information
: automatic control
floating Voltage: 53.500V
equalizing time
: 1
AH
80C
battery temperature test lower: -20C
: 80mV
7 EPS75-4815AF Monitoring Solution
: 60 days