Huawei UA5000 Manual page 123

Environment monitoring
Hide thumbs Also See for UA5000:
Table of Contents

Advertisement

UA5000 Universal Access Unit
Environment Monitoring
2.
3.
4.
Issue 01 (2012-08-17)
Query the status of the EPS75-4815AF.
huawei(config)#display emu 0
--------------------------------------------------------------------
EMU name
: POWER4875L
EMU type
: Pwr4875
EMU state
: Normal
Frame ID
: 0
Subnode
: 0
COM Port
: RS232
--------------------------------------------------------------------
Enter the environment monitoring configuration mode and query the default configuration.
huawei(config)#interface emu 0
huawei(config-if-power4875l-0)#display power system parameter
EMU ID: 0
----------------------------------------------------------------------------
charge control state
equalizing Voltage : 56.500V
charge lmt quotiety: 0.150
battery number
battery 0 capacity : 65
battery temperature test upper :
temperature redeem quotiety
battery temperature alarm upper:
load off permit
battery off permit : permit
AC over alarm voltage
DC over alarm voltage
power module number: 5
module 0 address: 1
module 1 address: 2
module 2 address: 3
module 3 address: 4
module 4 address: 5
Load high-temperature-off permit: forbid
Load high-temperature-off temperature(C): 65
Battery high-temperature-off permit: forbid
Battery high-temperature-off temperature(C): 53
----------------------------------------------------------------------------
huawei(config-if-power4875l-0)#display power environment parameter
EMU ID: 2
parameter
----------------------------------------------------------------------------
AnalogID Name
Type
0
Temperature
Current
1
Humidity
Current
----------------------------------------------------------------------------
DigitalID Name
Level
0
-
1
2
-
1
4
-
1
6
-
1
----------------------------------------------------------------------------
The results show that the power, temperature, and humidity parameters have been
configured automatically in the system; however, certain parameters need to be modified,
and certain extended monitoring parameters need to be added.
Configure the battery charging parameters.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Power system information
: automatic control
floating Voltage: 53.500V
equalizing time
: 1
AH
80C
battery temperature test lower: -20C
: 80mV
50C
battery temperature alarm lower: 0C
: forbid
load off voltage
battery off voltage : 43.000V
: 280V
AC lack alarm voltage : 180V
: 58 V
DC lack alarm voltage : 45V
module 0 switch state
module 1 switch state
module 2 switch state
module 3 switch state
module 4 switch state
Power environment configration
AlmUpper AlmLower TestUpper TestLower Unit
50
0
80
10
Level
|DigitalID Name
1
|
1
|
1
|
7 EPS75-4815AF Monitoring Solution
: 60 days
: 44.000V
: On
: On
: On
: On
: On
80
-20
100
0
1
-
3
-
5
-
C
%R.H.
117

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents