Huawei UA5000 Manual page 48

Environment monitoring
Hide thumbs Also See for UA5000:
Table of Contents

Advertisement

UA5000 Universal Access Unit
Environment Monitoring
4.
5.
6.
7.
Issue 01 (2012-08-17)
----------------------------------------------------------------------------
COM ID
Command BaudRate
0
-
-
1
-
-
PowerNumber
: 0
Battery off permission: Permit
Battery0 capacity: 100A
----------------------------------------------------------------------------
The results show that certain monitoring parameters, such as temperature, voltage, door
status, and MDF, have been configured automatically in the system. Other monitoring
parameters, however, need to be configured manually.
Configure the analog parameters.
huawei(config-if-h304esc-0)#esc analog 0 alarm-upper-limit 50 alarm-lower-
limit 5
huawei(config-if-h304esc-0)#esc analog 5 alarm-upper-limit 80 alarm-lower-
limit 0 name Humidity sensor-type 0:voltage analog-alarm 2 unit %RH
Configure the digital parameters.
huawei(config-if-h304esc-0)#esc digital 2 available-level low-level name SPD1
huawei(config-if-h304esc-0)#esc digital 3 available-level low-level name SPD2
huawei(config-if-h304esc-0)#esc digital 4 available-level low-level name SW1
huawei(config-if-h304esc-0)#esc digital 5 available-level low-level name SW2
huawei(config-if-h304esc-0)#esc digital 6 available-level low-level name SW3
huawei(config-if-h304esc-0)#esc digital 8 available-level low-level name fan1
huawei(config-if-h304esc-0)#esc digital 9 available-level low-level name fan2
huawei(config-if-h304esc-0)#esc digital 10 available-level low-level name fan3
huawei(config-if-h304esc-0)#esc digital 11 available-level low-level name fan4
Query the environment information, and confirm that the environment monitoring
functions are normal and the door status alarm other than alarms for other monitoring
parameters is generated.
huawei(config-if-h304esc-0)#display esc environment info
EMU ID: 0
FAN control mode :Auto
---------------------------Analog environment info--------------------------
ID Name
0
Temperature
1
-
2
-
3
-
4
Supply_Voltage
5
Humidity
6
-
7
-
---------------------------Digital environment info
ID Name
0
Wiring
2
SPD1
4
SW1
6
SW3
8
fan1
10 fan3
12 -
14 -
16 -
18 -
20 -
----------------------------------------------------------------------------
NOTE
Door status alarm "Door0" is generated because the door is open. At this time, if you turn on the
buzzer on the front panel of the H304ESC board, the buzzer generates a buzzing tone.
Save the data.
huawei(config-if-h304esc-0)#quit
huawei(config)#save
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
DataLength
StopLength
-
-
-
-
PowerType
: -
Battery off voltage: 43.2V
Battery1 capacity: 100A
ESC environment state
FAN run state: Close
State
Value
AlmUpper
Normal
29.00
55
Normal
0.00
127
Normal
0.00
127
Normal
-128.00
127
Normal
52.73
75
Normal
30.98
80
Normal
-128.00
127
Normal
-128.00
127
State
Value |ID Name
Normal 1
|1
Door0
Normal 0
|3
SPD2
Normal 0
|5
SW2
Normal 0
|7
-
Normal 0
|9
fan2
Normal 0
|11 fan4
Normal 1
|13 -
Normal 1
|15 -
Normal 1
|17 -
Normal 1
|19 -
Normal 1
|21 -
4 H304ESC Monitoring Solution
ParityType
-
-
Equalizing time: 60days
Battery charge state: Floating
AlmLower
Unit
5
C
-128
-
-128
-
-128
-
45
Volt
0
-
-128
-
-128
-
State
Alarm
Normal 0
Normal 0
Normal 1
Normal 0
Normal 0
Normal 1
Normal 1
Normal 1
Normal 1
Normal 1
Value
1
42

Hide quick links: