Huawei UA5000 Manual page 44

Environment monitoring
Hide thumbs Also See for UA5000:
Table of Contents

Advertisement

UA5000 Universal Access Unit
Environment Monitoring
Item
Issue 01 (2012-08-17)
Data
Valid level of digital
parameter 0: high level
Digital parameter ID: 1
Valid level of digital
parameter 1: low level
Digital parameter ID: 2
Valid level of digital
parameter 2: low level
Digital parameter ID: 3
Valid level of digital
parameter 3: low level
Digital parameter ID: 4
Valid level of digital
parameter 4: low level
Digital parameter ID: 5
Valid level of digital
parameter 5: low level
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
4 H304ESC Monitoring Solution
Remarks
When the high level represents the valid
level, the host does not report an alarm in the
case of high level.
The monitoring digital parameter of the door
status sensor is set here to monitor the door
status. When the cabinet door is opened, the
host reports an alarm.
Allocated by default (unable to be changed
by the user).
When the low level represents the valid level,
the host does not report an alarm in the case
of low level.
The monitoring digital parameter of the
surge protection circuit of the first DC input
is set here to monitor the status of the
protection circuit. When the protection
circuit fails, the host reports an alarm.
When the low level represents the valid level,
the host does not report an alarm in the case
of low level.
The monitoring digital parameter of the
surge protection circuit of the second DC
input is set here to monitor the status of the
protection circuit. When the protection
circuit fails, the host reports an alarm.
When the low level represents the valid level,
the host does not report an alarm in the case
of low level.
The monitoring digital parameter of SW1 is
set here to monitor the status of SW1. When
SW1 is turned off, the host reports an alarm.
When the low level represents the valid level,
the host does not report an alarm in the case
of low level.
The monitoring digital parameter of SW2 is
set here to monitor the status of SW2. When
SW2 is turned off, the host reports an alarm.
When the low level represents the valid level,
the host does not report an alarm in the case
of low level.