Huawei UA5000 Manual page 25

Environment monitoring
Hide thumbs Also See for UA5000:
Table of Contents

Advertisement

UA5000 Universal Access Unit
Environment Monitoring
Item
Issue 01 (2012-08-17)
Data
Digital parameter ID: 1
Valid level of digital
parameter 1: low level
Digital parameter ID: 2
Valid level of digital
parameter 2: low level
Digital parameter ID: 3
Valid level of digital
parameter 3: low level
Digital parameter ID: 4
Valid level of digital
parameter 4: low level
Digital parameter ID: 5
Valid level of digital
parameter 5: low level
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
3 H303ESC Monitoring Solution
Remarks
The monitoring digital parameter of the door
status sensor is set here to monitor the door
status. When the cabinet door is opened, the
host reports an alarm.
Allocated by default (unable to be changed
by the user).
When the low level represents the valid level,
the host does not report an alarm in the case
of low level.
This digital parameter is set according to the
actual requirements. The monitoring digital
parameter of the fan tray is set here to
monitor the status of the fan tray. When the
fan tray is faulty, the host reports an alarm.
When the low level represents the valid level,
the host does not report an alarm in the case
of low level.
This digital parameter is set according to the
actual requirements. The monitoring digital
parameter of the fan tray is set here to
monitor the status of the fan tray. When the
fan tray is faulty, the host reports an alarm.
When the low level represents the valid level,
the host does not report an alarm in the case
of low level.
This digital parameter is set according to the
actual requirements. The monitoring digital
parameter of the fan tray is set here to
monitor the status of the fan tray. When the
fan tray is faulty, the host reports an alarm.
When the low level represents the valid level,
the host does not report an alarm in the case
of low level.
This digital parameter is set according to the
actual requirements. The monitoring digital
parameter of the fan tray is set here to
monitor the status of the fan tray. When the
fan tray is faulty, the host reports an alarm.
When the low level represents the valid level,
the host does not report an alarm in the case
of low level.