Huawei UA5000 Manual page 62

Environment monitoring
Hide thumbs Also See for UA5000:
Table of Contents

Advertisement

UA5000 Universal Access Unit
Environment Monitoring
To...
Configure the digital parameters
The following considers the configuration in the M200 cabinet as an example to describe the
process of configuring the environment monitoring parameters of the ESCM.
1.
2.
3.
4.
Issue 01 (2012-08-17)
Log in to the UA5000 through the maintenance terminal and add an EMU.
huawei(config)#emu add 0 MiniESC 0 30 rs232 MiniESC
Enter the ESCM configuration mode and query the default analog and digital parameters.
huawei(config)#display emu 0
EMU ID: 0
----------------------------------------------------------------------------
EMU name
: MiniESC
EMU type
: MiniESC
Used or not : Used
EMU state
: Normal
Frame ID
: 0
Subnode
: 30
COM port
: RS232
Enter the ESCM configuration mode and query the default analog and digital parameters.
huawei(config)#interface emu 0
huawei(config-if-MiniESC-0)#display esc system parameter
EMU ID: 0
----------------------------------------------------------------------------
FAN run mode: Auto
C
AnalogID Name
0
Temperature
1
Input_-48V_0
2
-
3
-
----------------------------------------------------------------------------
DigitalID Name
0
Wiring
2
-
4
-
6
-
8
-
----------------------------------------------------------------------------
The results show that certain monitoring parameters, such as temperature, voltage, door
status, and MDF, have been configured automatically in the system. Other monitoring
parameters, however, need to be configured manually.
Configure the analog parameters.
huawei(config-if-MiniESC-0)#esc analog 0 alarm-upper-limit 50 alarm-lower-
limit 10
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Run the Command...
esc digital
IDs of user-defined alarms in the digital parameters: IDs
1-20 are reserved alarm IDs in the system (1:
AC_voltage; 2: AC_switch; 3: Battery_voltage; 4:
Battery_fuse; 5: Load_fuse; 6: Rectifier; 7: DC_power;
8: Cupboard_door; 9: Room_door; 10: Window; 11:
Theft; 12: Wiring; 13: Fan; 14: Fire; 15: Fog; 16: Water;
17: Diesel; 18: Smell 19: Air_conditioner; 20: SPD), and
IDs 21-52 are alarm IDs allocated to other user-defined
alarms by users.
ESC system parameter
Auto open temperature: 45 C
AlmUpper AlmLower TestHigh
55
5
75
45
127
-128
127
-128
Available Level|DigitalID Name
1
|
1
1
|
3
1
|
5
1
|
7
1
|
9
5 ESCM Monitoring Solution
Auto close temperature: 30
TestLow
Unit
100
-27
C
75
0
volt
127
-128
-
127
-128
-
Available Level
Door0
-
-
-
-
type
Voltage
Voltage
Voltage
Voltage
0
1
1
1
1
56

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents