UA5000 Universal Access Unit
Environment Monitoring
Item
Power
distribution
parameters
Battery test
parameters
Issue 01 (2012-08-17)
Data Plan for the
F01E400 Cabinet
AC overvoltage alarm
threshold of the power
supply: 280 V
AC undervoltage alarm
threshold of the power
supply: 180 V
DC overvoltage alarm
threshold of the power
supply: 58 V
DC undervoltage alarm
threshold of the power
supply: 45 V
Enables the battery auto-
discharging test
function: auto-
discharge-permit
Battery auto-
discharging test period:
180 d
Battery auto-
discharging start time: 0
h
Battery auto-
discharging duration: 2 h
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
6 EPS30-4815AF Monitoring Solution
Remarks
This parameter is set according to the actual
requirements. When the AC voltage exceeds the
preset overvoltage alarm threshold, the system
reports an AC overvoltage alarm. In this case, the
rectifier unit powers off automatically to protect
the system.
Default: 280 V.
This parameter is set according to the actual
requirements. When the AC voltage falls below
the preset undervoltage alarm threshold, the
system reports an AC undervoltage alarm. In this
case, the rectifier unit powers off automatically to
protect the system.
Default: 180 V.
This parameter is set according to the actual
requirements. When the DC voltage exceeds the
preset overvoltage alarm threshold, the system
reports a DC overvoltage alarm. In this case, the
rectifier unit powers off automatically to protect
the system.
Default: 58 V.
This parameter is set according to the actual
requirements. When the DC voltage falls below
the preset undervoltage alarm threshold, the
system reports a DC undervoltage alarm. In this
case, the rectifier unit powers off automatically to
protect the system.
Default: 45 V.
-
This parameter is set according to the actual
requirements.
Default: 120d.
This parameter is set according to the actual
requirements.
Default: 0h.
This parameter is set according to the actual
requirements.
Default: 2h.
74