Environment monitoring
Hide thumbs Also See for UA5000:
Table of Contents

Advertisement

UA5000 Universal Access Unit
Environment Monitoring
To...
Configure the digital
parameters
The following considers the configuration in the F02AF cabinet with the C-type PDU as an
example to describe the process of configuring the environment monitoring parameters of the
H304ESC board.
1.
2.
3.
Issue 01 (2012-08-17)
Log in to the UA5000 through the maintenance terminal and add an EMU.
huawei(config)#emu add 0 H304ESC 0 30 rs232 H304ESC
Query the status of the H304ESC board.
huawei(config)#display emu 0
EMU ID: 0
----------------------------------------------------------------------------
EMU name
: H304ESC
EMU type
: H304ESC
Used or not : Used
EMU state
: Normal
Frame ID
: 0
Subnode
: 30
COM port
: RS232
----------------------------------------------------------------------------
Enter the H304ESC configuration mode and query the default analog and digital
parameters.
huawei(config)#interface emu 0
huawei(config-if-h304esc-0)#display esc system parameter
EMU ID: 0
----------------------------------------------------------------------------
FAN run mode: Auto
AnalogID Name
0
Temperature
1
-
2
-
3
-
4
Supply_Voltage
5
-
6
-
7
-
----------------------------------------------------------------------------
DigitalID Name
0
Wiring
2
-
4
-
6
-
8
-
10
-
12
-
14
-
16
-
18
-
20
-
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Run the Command...
esc digital
IDs of user-defined alarms in the digital parameters: IDs 1-20
are reserved alarm IDs in the system (1: AC_voltage; 2:
AC_switch; 3: Battery_voltage; 4: Battery_fuse; 5: Load_fuse;
6: Rectifier; 7: DC_power; 8: Cupboard_door; 9: Room_door;
10: Window; 11: Theft; 12: Wiring; 13: Fan; 14: Fire; 15: Fog;
16: Water; 17: Diesel; 18: Smell 19: Air_conditioner; 20: SPD),
and IDs 21-52 are alarm IDs allocated to other user-defined
alarms by users.
ESC system parameter
Auto open temperature: 45 C
AlmUpper AlmLower TestUpper TestLower Unit
55
5
127
-128
127
-128
127
-128
75
45
127
-128
127
-128
127
-128
Level
|DigitalID Name
1
|
1
1
|
3
1
|
5
1
|
7
1
|
9
1
|
11
1
|
13
1
|
15
1
|
17
1
|
19
1
|
21
4 H304ESC Monitoring Solution
Auto close temperature: 30 C
100
-27
C
127
-128
-
127
-128
-
127
-128
-
100
0
Volt
127
-128
-
127
-128
-
127
-128
-
Door0
-
-
-
-
-
-
-
-
-
-
Type
Voltage
Voltage
Voltage
Voltage
Voltage
Voltage
Voltage
Voltage
Level
0
1
1
1
1
1
1
1
1
1
1