Huawei UA5000 Manual page 63

Environment monitoring
Hide thumbs Also See for UA5000:
Table of Contents

Advertisement

UA5000 Universal Access Unit
Environment Monitoring
5.
6.
7.
8.
Issue 01 (2012-08-17)
huawei(config-if-MiniESC-0)#esc analog 2 alarm-upper-limit 80 alarm-lower-
limit 0 name Humidity sensor-type 0:voltage analog-alarm 2 unit %RH
Configure the digital parameters.
huawei(config-if-MiniESC-0)#esc digital 9 available-level low-level name szl9
digital-alarm
7
Query the default configuration of the analog and digital parameters.
huawei(config-if-MiniESC-0)#display esc environment info
EMU ID: 0
FAN control mode :Auto
---------------------------Analog environment info--------------------------
ID Name
0
Temperature
1
Input_-48v_0
2
Humidity
3
-
---------------------------Digital environment
info---------------------------
ID Name
0
Wiring
2
-
4
-
6
-
8
-
----------------------------------------------------------------------------
NOTE
The door status alarm "Door0" is generated because the door is open.
Save the data.
huawei(config-if-MiniESC-0)#quit
huawei(config)#save
Close all the cabinet doors. Query the environment information again, and confirm that no
door status alarm is generated.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
ESC environment state
FAN run state: Open
State
Value
AlmUpper
Normal
29.00
50
Normal
53.906
75
Normal
-128.00
127
Normal
-128.00
127
State
Value |ID Name
Normal 1
|1
Door0
Normal 1
|3
-
Normal 1
|5
-
Normal 1
|7
-
Normal 1
|9
szl9
5 ESCM Monitoring Solution
AlmLower
Unit
10
C
45
V
-128
-
-128
-
State
Value
Alarm
1
Normal 1
Normal 1
Normal 1
Normal 0
57