Huawei UA5000 Manual page 153

Environment monitoring
Hide thumbs Also See for UA5000:
Table of Contents

Advertisement

UA5000 Universal Access Unit
Environment Monitoring
4.
5.
6.
7.
8.
9.
Issue 01 (2012-08-17)
battery temperature test upper :
temperature redeem quotiety
battery temperature alarm upper:
load off permit
battery off permit : permit
AC over alarm voltage
DC over alarm voltage
power module number: 5
module 0 address: 1
module 1 address: 2
module 2 address: 3
module 3 address: 4
module 4 address: 5
Load high-temperature-off permit: forbid
Load high-temperature-off temperature(C): 65
Battery high-temperature-off permit: forbid
Battery high-temperature-off temperature(C): 53
----------------------------------------------------------------------------
huawei(config-if-power4875l-0)#display power environment parameter
EMU ID: 2
parameter
----------------------------------------------------------------------------
AnalogID Name
Type
0
Temperature
Current
----------------------------------------------------------------------------
DigitalID Name
Level
0
-
1
2
-
1
4
-
1
6
-
1
----------------------------------------------------------------------------
The results show that the power, temperature, and humidity parameters have been
configured automatically in the system; however, certain parameters need to be modified,
and certain extended monitoring parameters need to be added.
Configure the battery charging parameters.
If the planned data is the same as the query result, the parameters need not be configured.
If the parameters need to be modified, run the power charge command.
Configure the battery management parameters.
huawei(config-if-power4875l-0)#power battery parameter 0.15 60 1 150
Configure the temperature compensation coefficient of the battery.
If the planned data is the same as the query result, the parameters need not be configured.
If the parameters need to be modified, run the power battery temperature command.
Configure the power supply load power-off and battery set power-off parameters.
If the planned data is the same as the query result, the parameters need not be configured.
If the parameters need to be modified, run the power off command.
Configure the power distribution parameters.
If the planned data is the same as the query result, the parameters need not be configured.
If the parameters need to be modified, run the power supply-parameter command.
Configure the battery discharging test parameters.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
80C
battery temperature test lower: -20C
: 80mV
50C
battery temperature alarm lower: 0C
: forbid
load off voltage
battery off voltage : 43.000V
: 280V
AC lack alarm voltage : 180V
: 58 V
DC lack alarm voltage : 45V
module 0 switch state
module 1 switch state
module 2 switch state
module 3 switch state
module 4 switch state
Power environment configration
AlmUpper AlmLower TestUpper TestLower Unit
50
0
Level
|DigitalID Name
1
|
1
|
1
|
8 ETP4890 Monitoring Solution
: 44.000V
: On
: On
: On
: On
: On
80
-20
1
-
3
-
5
-
C
147