UA5000 Universal Access Unit
Environment Monitoring
Configuration Process
The monitoring parameters can be reported to the control board only when the data of the
H304ESC board is correctly configured in the system.
process, and
Figure 4-5 Configuration process of the H304ESC board
Table 4-11 Commands for configuring the H304ESC board
To...
Add an EMU
Query the status of the
EMU
Query the system
configuration
Query the environment
information
Configure the analog
parameters
Issue 01 (2012-08-17)
Table 4-11
lists the commands used during the configuration.
Start
Add the EMU
Query the EMU status
Query the default monitoring
information
configure the environment
monitoring parameters
Query the environment
information
Confirm the environment
information
End
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Run the Command...
emu add
display emu
display esc system parameter
display esc environment info
esc analog
IDs of user-defined alarms in the analog parameters: IDs 1-4 are
reserved alarm IDs in the system (1: temperature; 2: humidity;
3: voltage; 4: current), and IDs 5-20 are alarm IDs allocated to
other user-defined alarms by users.