Huawei UA5000 Manual page 152

Environment monitoring
Hide thumbs Also See for UA5000:
Table of Contents

Advertisement

UA5000 Universal Access Unit
Environment Monitoring
To...
Configure the rectifier unit
parameter
Configure the load and battery
high-temperature power-off
parameters
Configure the environment
monitoring parameters
Configure the external extended
digital parameters
Query the configuration
parameters of the power system
The following considers the configuration in the F01D500 cabinet as an example to describe the
process of configuring the environment monitoring parameters of the ETP4890.
1.
2.
3.
Issue 01 (2012-08-17)
NOTE
The ETP4890 power system is managed as the EPS75-4815AF power system. To differentiate the ETP4890
power system from the EPS75-4815AF power system, run the display version command. Specifically, the
version of the ETP4890 environment monitoring unit (EMU) is 3xxx and that of the EPS75-4815AF EMU
is 1xxx.
Log in to the PVM through the maintenance terminal and add an EMU.
huawei(config)#emu add 0 POWER4875L 0 0 RS301 ETP4890
Query the status of the ETP4890.
huawei(config)#display emu 0
--------------------------------------------------------------------
EMU name
: ETP4890
EMU type
: Pwr4875
EMU state
: Normal
Frame ID
: 0
Subnode
: 0
COM Port
: RS301
--------------------------------------------------------------------
Enter the environment monitoring configuration mode and query the default configuration.
huawei(config)#interface emu 0
huawei(config-if-power4875l-0)#display power system parameter
EMU ID: 0
----------------------------------------------------------------------------
charge control state
equalizing Voltage : 56.500V
charge lmt quotiety: 0.150
battery number
battery 0 capacity : 65
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Run the Command...
power module-num
power temperature-off
power environment
power outside-digital
IDs of user-defined alarms in the digital parameters: IDs
1-20 are reserved alarm IDs in the system (1: AC_voltage;
2: AC_switch; 3: Battery_voltage; 4: Battery_fuse; 5:
Load_fuse; 6: Rectifier; 7: DC_power; 8: Cupboard_door;
9: Room_door; 10: Window; 11: Theft; 12: Wiring; 13:
Fan; 14: Fire; 15: Fog; 16: Water; 17: Diesel; 18: Smell
19: Air_conditioner; 20: SPD), and IDs 21-52 are alarm
IDs allocated to other user-defined alarms by users.
display power system parameter
Power system information
: automatic control
floating Voltage: 53.500V
equalizing time
: 1
AH
8 ETP4890 Monitoring Solution
: 60 days
146

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents